NO TICE
Ensure that the rubber ring is not disconnected. If the rubber ring is disconnected
or damaged, seal the gaps around the pipes with mastic cement or thermal
insulation foam.
Step 3 Connect the gas and liquid pipes to the gas and liquid pipes of the outdoor unit
respectively.
Step 4 Wrap the thermal insulation foam.
----End
4.8.3 Connecting Outdoor Unit Pipes
NO TICE
1. Before welding refrigerant pipes, fully exhaust nitrogen from the refrigerant
pipes to avoid explosion and injuries.
2. When you welding pipes, pay attention to protecting surrounding components
and cables.
Step 1 Remove the plugs using a welding torque.
Step 2 Connect the gas and liquid pipes to the gas and liquid pipes of the indoor unit
respectively.
Step 3 Wrap the thermal insulation foam.
Figure 4-66 Welding outdoor unit pipes (for NetCol500-A060)
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual