6.5.2 (Optional) Setting the Pressure Difference Control
Prerequisites
If the differential pressure sensors are installed, perform the following operations
accordingly. If the differential pressure sensors are not installed, skip this part.
Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor fan, set Air-
side difference pressure sensor type to 0~500 Pa comm port.
Step 2 Set Indoor fan control type to Pressure diff ctrl.
Step 3 Change the other parameters based on the following instructions.
Parameter
Description
Indoor fan control
type
● Return/supply air temperature difference proportion
control: controls the indoor fan speed based on the
proportion of temperature difference between
return air and supply air.
● Return/supply air temperature difference control:
controls the indoor fan speed based on the
temperature difference between return air and
supply air.
● Pressure difference control: controls the indoor fan
speed based on the pressure difference.
Indoor fan silent
mode
● Disable: The silent mode is disabled.
● Enable: The fan enters the silent mode. The
maximum rotational speed of the fan is limited, and
the fan running sound is reduced.
Air-side differential
pressure sensor type
Select the proper differential pressure sensor type
based on the measurement range of the differential
pressure sensor.
Min indoor fan speed
Specifies the minimum rotational speed of the indoor
fan.
Max indoor fan speed
Specifies the maximum rotational speed of the indoor
fan.
----End
6.5.3 (Optional) Setting Teamwork Parameters
Prerequisites
The teamwork group number and addresses for the units have been set as follows:
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual