Figure 4-7 Installation modes (NetCol500-A110)
Special Environmental Requirements
●
Monsoon: If you install the outdoor unit vertically, ensure that the air
produced by fans flows in and out in the same direction as the monsoon.
●
Direct sunlight: In high-temperature areas, avoid exposing the outdoor unit to
direct sunlight.
●
Wind and sand: Prevent sand from entering the condenser in deserts and
windy and sandy areas.
Space Requirements
The NetCol500 outdoor unit supports three installation modes: horizontal
installation, vertical installation, and compact installation.
,
, and
show the horizontal and vertical installation.
, and
show the compact outdoor unit installation requirements.
The NetCol500-A110 outdoor unit does not support vertical installation.
shows the horizontal installation.
shows the compact outdoor
unit installation requirement.
The outdoor unit should be installed against a wall if possible when it is installed
vertically. If the site does not meet the requirements and the local outdoor
temperature is lower than –5°C, add an air baffle. The height and width of the air
baffle must be greater than or equal to those of the outdoor unit.
NO TE
● The shaded parts in the figures are obstacles. The distances marked are the minimum
distances required between an outdoor unit and obstacles.
● The NetCol500-A080 and NetCol500-A110 are used as an example to illustrate
horizontal installation. The NetCol500-A080 is used as an example to illustrate vertical
installation.
Horizontal and vertical installation scenarios
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
4 System Installation
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
57