Alarm ID
Alarm Name
Alarm
Severity
Possible Cause
Solution
A222-01
Main control module
power supply
abnormal
Major
● The system is
powered off.
● The main control
module is in poor
contact.
● The auxiliary power
supply is faulty.
● The auxiliary power
supply is in poor
contact.
● The main control
module is faulty.
1. Power on the
system.
2. Check the
interconnection
module in the main
control module.
3. Replace the
auxiliary power
supply.
4. Check the
interconnection
module of the
auxiliary power
supply.
5. Replace the main
control module.
A233-01
Air-side low pressure
difference alarm
Warning
● Contained aisles
are poorly-sealed.
● The differential
pressure sensor is
faulty.
1. Check that the cold
and hot aisles are
well-sealed.
2. Maintain or replace
the differential
pressure sensor.
A242-01
Manual shutdown
alarm
Major
The air conditioner is
shut down via the LCD
or NetEco.
Restart the air
conditioner via the
LCD or NetEco.
A26B-01
A26B-04
Indoor fan 1 power
supply abnormal
Indoor fan 2 power
supply abnormal
Major
● The cable to the
fan is not
connected properly.
● The fan drive is
faulty.
1. Check the cable
connection to the
fan.
2. If the drive is
integrated into the
fan, replace the
fan.
If the drive is
separate from the
fan, replace the
drive.
A26B-02
Indoor fan 1 power
supply abnormal
Indoor fan 2 power
supply abnormal
Major
The fan drive is faulty.
If the drive is
integrated into the
fan, replace the fan.
If the drive is separate
from the fan, replace
the drive.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
10 Alarm Reference
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
239