Figure 11-4 Removing the drive (for NetCol8000-A045D)
Step 5 Install the new drive and its cables.
Step 6 Turn on the smart cooling product switch in the PDF.
Step 7 Switch on the QF1 and QF2, and close the front door.
Step 8 After the home screen is displayed, choose Maint > Wizard Startup, start the
compressor, and check that the compressor runs properly and no alarm is
generated. Check that it works properly before you exit.
----End
11.4 Replacing a Fan Drive (NetCol8000-A055/A060/
A120)
Prerequisites
●
A drive needs to be replaced.
●
A spare fan drive of the same model is available and functional.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual