Alarm ID
Alarm Name
Alarm
Severity
Possible Cause
Solution
A293-01
A293-04
Outdoor fan 1 power
supply abnormal
Outdoor fan 2 power
supply abnormal
Major
● A power grid input
cable is loose.
● The power grid
voltage is below
the lower
threshold.
● The outdoor fan
drive is faulty.
1. Secure the power
grid input cable.
2. Power off the
system and check
that the power grid
input voltage meets
the specifications.
3. Replace the
outdoor fan drive.
A293-02
A293-08
Outdoor fan 1 power
supply abnormal
Outdoor fan 2 power
supply abnormal
Major
The power grid
voltage exceeds the
upper threshold.
Power off the system
and check that the
power grid input
voltage meets the
specifications.
A293-10
Outdoor fan 1 power
supply abnormal
Outdoor fan 2 power
supply abnormal
Major
The power grid
frequency is abnormal.
Power off the system
and check that the
input power frequency
meets the
specifications.
A294-02
A294-04
A294-08
Outdoor fan 1 drive
overcurrent alarm
Outdoor fan 2 drive
overcurrent alarm
Major
● The outdoor fan is
faulty.
● The outdoor fan
drive is faulty.
1. Replace the
outdoor fan.
2. Replace the
outdoor fan drive.
A295-02
Outdoor fan 1 fault
Outdoor fan 2 fault
Major
● The
overtemperature
feedback cable to
the outdoor fan is
loose.
● The outdoor unit is
dirty or blocked.
● The outdoor fan is
faulty.
● The outdoor fan
drive is faulty.
1. Secure the
overtemperature
feedback cable to
the outdoor fan.
2. Clear obstacles
from the outdoor
fan to ensure that
it works properly.
3. Replace the
outdoor fan.
4. Replace the
outdoor fan drive.
A295-10
Outdoor fan 1 fault
Outdoor fan 2 fault
Major
The output cable to
the outdoor fan drive
is grounded.
Replace the output
cable to the outdoor
fan drive.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
10 Alarm Reference
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
253