4.11.4.3 CAN Te FE Monitoring
Step 1 Connect teamwork and monitoring communications cables.
Networking
CAN Teamwork
FE Monitoring
Protocol
CAN
Modbus-TCP/SNMP
Description
One teamwork network
supports a maximum of 32
units. On the Teamwork
Settings screen of the display
modules of the first and last
units, set Enable teamwork
CAN resistor to Yes.
-
NO TE
Customers can purchase a switch and NetEco as the monitoring system.
Figure 4-109 Connecting communications cables
----End
4.11.4.4 FE Te RS485 Monitoring
Step 1 Connect teamwork and monitoring communications cables.
Networking
FE Teamwork
RS485 Monitoring
Protocol
MAC_CAN
Modbus-RTU
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual