Alarm ID
Alarm Name
Alarm
Severity
Possible Cause
Solution
A185-01
Compressor 1
insufficient refrigerant
alarm
Compressor 2
insufficient refrigerant
alarm
Warning
● Refrigerant has
leaked.
● Refrigerant is not
charged as required
in the user manual.
● The displayed
values of the liquid
pipe temperature
sensor or the
condensing
pressure sensor on
the LCD are
different from the
actual values.
● The expansion
valve is blocked or
stuck, or the
expansion valve coil
and cable
connections are
faulty.
1. Check the system
for leaking points.
If so, repair the
pipe and add
refrigerant.
2. Add refrigerant as
required in the user
manual.
3. Calibrate or replace
the liquid pipe
temperature sensor
or the condensing
pressure sensor.
4. Maintain or replace
the expansion valve
or the coil, and
reconnect cables.
A193-01
Air-side diff pressure
sensor fault
Major
● The cable to the
differential pressure
sensor is loose or
damaged.
● The pressure tube
of the differential
pressure sensor is
reversely
connected.
1. Check the cable
connection to the
differential pressure
sensor.
2. Check the tube
connection to the
differential pressure
sensor.
A208-01
Indoor fan 1 blocked
alarm
Indoor fan 2 blocked
alarm
Major
● The fan blade is
stuck.
● The fan is faulty.
1. Clear the blockage.
2. Maintain or replace
the fan.
A220-01
Wizard startup is in
progress
Warning
Wizard startup is in
progress.
Wait until wizard
startup is complete or
clear the alarm
manually to exit
wizard startup.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
10 Alarm Reference
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
238