Table 4-3 Recommended cables
Item
NetCol800
0-A045
NetCol800
0-A055/
A060
NetCol80
00-A090
NetCol80
00-A120
Equipotenti
al ground
cable
Recommend
ed cable
16 mm
2
16 mm
2
16 mm
2
16 mm
2
Active
power cable
for the
indoor unit
Maximum
current
40 A
41 A
80 A
82 A
Recommend
ed upstream
circuit
breaker
50 A/3P
(characteri
stics of C)
63 A/3P
(characteri
stics of C)
100 A/3P
(character
istics of C)
125 A/3P
(character
istics of C)
Rec
om
me
nde
d
cab
le
L1/L2/
L3/N
5 x 10
mm
2
5 x 10
mm
2
4 x 25
mm
2
4 x 25
mm
2
PE
16 mm
2
16 mm
2
Standby
power cable
for the
indoor unit
Maximum
current
36 A
41 A
72 A
82 A
Recommend
ed upstream
circuit
breaker
50 A/3P
(characteri
stics of C)
63 A/3P
(characteri
stics of C)
100 A/3P
(character
istics of C)
125 A/3P
(character
istics of C)
Rec
om
me
nde
d
cab
le
L1/L2/
L3/N
5 x 10
mm
2
5 x 10
mm
2
4 x 25
mm
2
4 x 25
mm
2
PE
16 mm
2
16 mm
2
Outdoor
unit power
cable
Rec
om
me
nde
d
cab
le
L1/L2/
L3/PE
4 x 2.5
mm
2
4 x 2.5
mm
2
4 x 2.5
mm
2
4 x 2.5
mm
2