Alarm ID
Alarm Name
Alarm
Severity
Possible Cause
Solution
A094-01
Low humidity alarm
Warning
● The ambient
humidity is below
the lower
threshold.
● The temperature
and humidity
sensor is not
installed in a
proper position.
● The low humidity
alarm threshold is
inappropriate.
● The value detected
by the temperature
and humidity
sensor is different
from the actual
value.
1. Measure the
ambient humidity.
2. Adjust the position
of the temperature
and humidity
sensor.
3. Adjust the low
humidity alarm
threshold.
4. Calibrate or replace
the temperature
and humidity
sensor.
A118-01
Backup power failure
alarm
Primary power failure
alarm
Major
The power supply is
faulty.
Check the power
supply.
A120-01
Indoor fan 1
communication failed
Indoor fan 2
communication failed
Major
● The
communications
cable to the fan is
not connected
properly.
● The fan drive is
faulty.
1. Check the
communications
cable connection to
the fan.
2. If the drive is
integrated into the
fan, replace the
fan.
If the drive is
separate from the
fan, replace the
drive.
A134-01
Compressor 1 suction
temperature sensor
fault
Compressor 2 suction
temperature sensor
fault
Major
● The cables to the
suction
temperature sensor
are loose or
damaged.
● The suction
temperature sensor
is faulty.
1. Check cables to the
suction
temperature sensor.
2. Maintain or replace
the suction
temperature sensor.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
10 Alarm Reference
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
234