12.3.14 How Do I Set Alarm Parameters?
Prerequisites
Before setting the alarm parameters, get familiar with the coupling relationship
among each parameter.
Configurations of temperature and humidity alarms and main board settings for
the air-cooled devices should comply with the following coupling relationships:
●
Power supply underfrequency alarm threshold < Power supply overfrequency
alarm threshold
●
Standby power underfrequency alarm threshold < Standby power
overfrequency alarm threshold
●
Supply air high temperature alarm thr 5°C ≤ Return air high
temperature alarm threshold
●
Supply air high temperature alarm thr 5°C ≤ Hot aisle high
temperature alarm threshold
●
Cold aisle high temperature alarm thr 5°C ≤ Hot aisle high
temperature alarm threshold
●
Cold aisle high temperature alarm thr 5°C ≤ Return air high
temperature alarm threshold
●
Supply air low temperature alarm thr 5°C ≤ Return air low
temperature alarm threshold
Context
●
This section describes how to set an alarm threshold.
●
All alarm thresholds are configured in the same way. This section describes
how to set the threshold of Return air high temperature alarm for the T/H
sensor.
●
If you need to change alarm settings, log in as user Admin.