Item
Check that
Troubleshooting
Remarks
Electric
control
system
Cables are
connected properly.
Secure the
terminals.
Check and perform
the troubleshooting
with the power off.
The cable holes of
the electrical control
box are properly
sealed.
Check whether the
waterproof
connector is aging,
if yes, replace a new
one.
Check and perform
the troubleshooting
with the power off.
Cables are not
damaged or aged.
Replace the cables.
Check and perform
the troubleshooting
with the power off.
The electrical
control box is free
from water.
Clean up the water
in the box and
check the reason for
leaking.
Check and perform
the troubleshooting
with the power off.
Low-
temperatur
e
component
(optional)
Bolts are properly
tightened.
Tighten bolts.
Check and perform
the troubleshooting
with the power off.
Cables are securely
connected.
Check the cable
connection. If the
cable is loose,
secure it.
Check and perform
the troubleshooting
with the power off.
8.4 Water Cooling Module Routine Maintenance
8.4.1 Monthly Maintenance
Table 8-7 Monthly maintenance items
Item
Expected Result
Troubleshooting
Remarks
Refrigerant
pipe
The refrigerant
pipes are secured.
Secure the pipe
support
Perform the
troubleshooting
with the power off.
All refrigerant pipes
are clean without
leaking and eroding
Drain the
refrigerant, and
repair the leakage
on the pipe.
Perform the
troubleshooting
with the power off.
The pipe thermal
insulation foam is
intact.
Wrap the thermal
insulation foam
again.
Perform the
troubleshooting
with the power off.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
8 Operation and Maintenance
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
214