Item
NetCol8000-A055D
Maximum operating current (A) - dual
power supplies
● With heating and humidification
– Active route: 45
– Standby route: 41
● Without heating and humidification
– Active route: 41
– Standby route: 41
Dimensions (H x W x D) (mm)
2000 x 900 x 1000
Air filter level
G4
Net weight (kg)
354
a: Tested under rated working conditions (indoor dry-bulb temperature: 35°C,
relative humidity: 26%; outdoor temperature: 35°C).
Table 3-3 Technical specifications of NetCol8000-A060/NetCol8000-A120
Item
NetCol8000-
A060D
NetCol8000-
A060U
NetCol8000-
A120D
Power supply
380–415 V AC, 3-phase, 50 Hz/60 Hz
Number of fans
1
1
2
Total cooling
capacity (kW)
a
60
60
120
Sensible cooling
capacity (kW)
a
60
60
120
Air volume (m
3
/h) 15000
14500
30000
(Optional)
Reheating
capacity (kW)
a
6
6
12
(Optional)
Humidification
capacity (kg/h)
a
6
6
10
Maximum
operating current
(A) - single power
supply
● With heating
and
humidification:
45
● Without
heating and
humidification:
41
● With heating
and
humidification:
45
● Without
heating and
humidification:
41
● With heating
and
humidification:
90
● Without
heating and
humidification:
82
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
3 Technical Specifications
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.