Alarm ID
Alarm Name
Alarm
Severity
Possible Cause
Solution
A296-01
EEV 1 low superheat
degree alarm
EEV 2 low superheat
degree alarm
Major
● The electronic
expansion valve
(EEV) coil is loose.
● The EEV coil is
faulty.
● The cables to the
EEV coil are loose
or damaged.
● The EEV is faulty.
1. Reinstall the EEV
coil.
2. Replace the EEV
coil.
3. Check and maintain
the cables to the
EEV coil.
4. Replace the EEV.
A296-02
EEV 1 low superheat
degree alarm
EEV 2 low superheat
degree alarm
Critical
● The electronic
expansion valve
(EEV) coil is loose.
● The EEV coil is
faulty.
● The cables to the
EEV coil are loose
or damaged.
● The EEV is faulty.
1. Reinstall the EEV
coil.
2. Replace the EEV
coil.
3. Check and maintain
the cables to the
EEV coil.
4. Replace the EEV.
A30C-01
A30C-02
A30C-04
Certificate is about to
expire
Warning
● The corresponding
certificate is about
to expire.
● The system time is
incorrectly set.
1. Apply for a new
certificate promptly
and update the
existing one.
2. Calibrate the
system time.
A30D-01
Certificate is not in
effect
Warning
● The installed
certificate does not
take effect.
● The connection of
the corresponding
certificate server is
abnormal.
● The corresponding
certificate is not
within the validity
period.
1. Ensure that the
certificate is
correctly installed.
2. Ensure that the
connection of the
certificate server is
normal.
3. Ensure that the
installed certificate
is within the
validity period.
A30E-01
A30E-02
A30E-04
Certificate has expired
Warning
● The corresponding
certificate has
expired.
● The system time is
incorrectly set.
1. Apply for a new
certificate promptly
and update the
existing one.
2. Calibrate the
system time.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
10 Alarm Reference
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
254