Item
Check that
Troubleshooting
Remarks
The thermal
insulator on the
refrigerant pipe is
not damaged.
Rewrap the thermal
insulator.
Perform the
troubleshooting
with the power off.
Condenser
The fins are not
pushed down.
Restore the fins by
using a wire brush.
Perform the
troubleshooting
with the power off.
The air intake
section of the
condenser and the
air exhaust section
of the fan are
unblocked.
Clean up obstacles
on the inlet and
outlet.
Perform the
troubleshooting
with the power off.
The fins are not
blocked.
Clean the fins.
Perform the
troubleshooting
with the power off.
8.3.2 Semi-annual Maintenance
Table 8-6 Semi-annual maintenance items
Item
Check that
Troubleshooting
Remarks
Rack
Ensure that the rack
is secured to the
ground.
Fasten the screws.
Perform the
troubleshooting
with the power off.
Fans
The fan connection
box is intact and
secured.
Secure the fan
connection box.
Check and perform
the troubleshooting
with the power off.
The net cover and
flow deflecting ring
are independent of
each other and not
deformed or
damaged.
Maintain or replace
the net cover.
Perform the
troubleshooting
with the power off.
The fan runs
smoothly without
abnormal voice or
vibration, and the
blades rotate in the
direction as the
symbols show.
Replace the fan.
Perform the
troubleshooting
with the power off.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
8 Operation and Maintenance
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
213