Tab
Parameter
Description
DO_1
● If this parameter is set to Smoke &
Water only, DO_1 acts according to
DO_1 action when a smoke or
water overflow alarm is generated.
● If this parameter is set to Critical
alarm, DO_1 acts according to
DO_1 action when a critical alarm
is generated.
● If this parameter is set to Major,
DO_1 acts according to DO_1
action when a major alarm is
generated.
● If this parameter is set to Alarm,
DO_1 acts according to DO_1
action when a critical alarm, major
alarm, or warning is generated.
● If this parameter is set to Startup
status, DO_1 acts according to
DO_1 action when the unit is
started.
● If this parameter is set to None, no
alarm is generated when DO_1 is
disconnected.
DO_2
For details, see DO_1 description.
Floor water overflow
alarm action
Set the action of the device if there is
water overflow on the floor based on
the actual scenario.
● Shutdown: The device shuts down
when a floor water overflow alarm
is generated.
● Inactivity: The device runs as usual
when a floor water overflow alarm
is generated.
● Only indoor fan running: Only the
indoor fan runs when a floor water
overflow alarm is generated.
● Humidifier stopped: Only the
humidifier is stopped when a floor
water overflow alarm is generated.