When the external conditions such as cable layout or ambient temperatures change,
perform verification in accordance with the IEC-60364-5-52 or the local regulations.
The recommended cables are applicable only when the following requirements are met:
● The cables are routed over a ladder or bracket in a single layer (E or F in IEC
60364-5-523). The distance between cables is greater than twice the cable diameter.
● The AC voltage loss is less than 3%.
● Single- or multi-core 90°C-resistant copper flexible cables are used.
Table 4-4 Power cable terminal requirements
Item
NetCol8000-A045/A055/A060/A090/A120
Terminal
L1/L2/L3/N
PE
Connection mode
Cord end terminal
OT terminal
Torque
2.0 N·m
4.5 N·m
4.3 Unpacking and Checking
Prerequisites
Move the smart cooling product to a place closest to the installation position and
then unpack it to facilitate cabinet movement and avoid cabinet damage.
Procedure
Step 1 Verify that the cabinet package is intact. If any damage is found, notify the carrier
immediately.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product