Alarm ID
Alarm Name
Alarm
Severity
Possible Cause
Solution
A146-01
Outdoor fan 1 blocked
alarm
Outdoor fan 2 blocked
alarm
Major
● The outdoor fan is
blocked.
● The outdoor fan is
faulty.
1. Clear obstacles
from the outdoor
fan to ensure that
it works properly.
2. Replace the
outdoor fan.
A147-01
Outdoor fan 1 drive
output phase
sequence abnormal
Outdoor fan 2 drive
output phase
sequence abnormal
Major
● The output cable
connector for the
outdoor fan drive
or the input cable
connector for the
outdoor fan is
loose.
● The output cable to
the outdoor fan
drive is
disconnected.
● The outdoor fan
drive is faulty.
● The outdoor fan is
faulty.
1. Secure the output
cable to the
outdoor fan drive.
2. Replace the output
cable to the
outdoor fan drive.
3. Replace the
outdoor fan drive.
4. Replace the
outdoor fan.
A162-01
Outdoor fan 1
pressure sensor fault
Outdoor fan 2
pressure sensor fault
Major
● A cable of the
pressure sensor is
loose.
● The pressure sensor
is faulty.
1. Tighten the
pressure sensor
cable connector.
2. Replace the
pressure sensor
A172-01
SPD and voltage
detection board comm
failed
Backup SPD and volt
detection board comm
failed
Major
● The
communications
cable is not
connected properly.
● The SPD and
voltage detection
board is faulty.
● The
communications
port of the main
control board is
faulty.
1. Check the
communications
cable.
2. Replace the SPD
and voltage
detection board.
3. Maintain or replace
the main control
board.
A174-01
SPD function failure
Backup SPD function
failed
Major
The SPD and voltage
detection board is
faulty.
Replace the SPD and
voltage detection
board.