Figure A-3 Signal terminals
Table A-1 Signal table
No.
x501
x502
x503
1
Smoke sensor power
supply (12 V DC)
Water leakage
detection (water
leakage from the
floor)+
Outdoor unit RS485+
for system 1
2
Smoke sensor
feedback
Water leakage
detection (water
leakage from the
floor)–
Outdoor unit RS485–
for system 1
3
Remote startup/
s
24 V DC power supply
Outdoor unit RS485–
GND for system 1
4
Remote startup/
shutdown–
Differential pressure
sensor GND
N/A
5
Common alarm 1+
Differential pressure
sensor 0–5 V feedback
Outdoor unit RS485+
for system 2
6
Common alarm 1–
Differential pressure
sensor 5 V DC
Outdoor unit RS485–
for system 2
7
Common alarm 2+
Reserved
Outdoor unit RS485–
GND for system 2
8
Common alarm 2–
Reserved
Reserved
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
A Electric Control Box Layout
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
308