Item
Technical Specifications
Temperature range
4–45
℃
Humidity range
5%–90% RH
Storage
temperature
–40°C to +70°C
Storage humidity
5%–95% RH (non-condensing)
Inlet cooling water
temperature range
10–37°C
Maximum
operating
temperature on the
refrigerant side
125°C
Maximum
operating
temperature on the
cooling water side
60°C
Water flow rate
9.5 m
3
/h
Water-side pressure 1.2 MPa
Refrigerant-side
pressure
4.35 MPa
IP rating
IP21
Altitude
0–4000 m, derated at 1000 m or above
Environment type
Enclosed indoor environment in which the temperature
and humidity can be controlled within the ranges of 4°C
to 45°C and 5% RH to 90% RH respectively. If the indoor
installation position is ventilated, it should be more than
3.7 km away from the sea or pollution sources (such as
salt lakes, chemical plants, mineral plants, thermal power
plants, and coal mines).
Net weight
63 kg
3.5 Operating Environment
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
3 Technical Specifications
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
46