Tab
Parameter
Description
System
Settings
Dual power supply
setting
Set this parameter as required.
● Primary power only: Select this
option when the dual-power model
is connected to the primary power
only.
● Primary power first: Select this
option when the dual-power model
is connected to two power supplies.
Outdoor unit
condensate mode
● Air-cooled: The outdoor unit is an
air-cooled outdoor unit.
● Water-cooled: The outdoor unit is a
water-cooled module.
Temp control
intelligent monitoring
board
A temperature control intelligent
monitoring board is used to monitor
the outdoor environment.
Check the cover of the electric control
box of the outdoor unit.
● If there is an intelligent
temperature control monitoring
board, set this parameter to Yes.
● If there is no intelligent
temperature control monitoring
board, set this parameter to No.
Smart diagnosis
function
● Enable: If there is an intelligent
temperature control monitoring
board, this function is enabled to
start refrigerant shortage detection.
● Disable: The smart diagnosis
function is disabled.
Conditions for starting refrigerant
shortage detection:
● No low temperature component is
configured.
● Altitude: ≤ 2000 m
● 7.5 m ≤ equivalent pipe length of
the one-way pipe ≤ 100 m
● –8 m ≤ vertical distance between
the indoor and outdoor units ≤ +30
m
● 5°C ≤ outdoor ambient temperature
≤ 40.5°C
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
6 Power-On Commissioning
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.