SPLIT SYSTEM AIR CONDITIONER  (R-410A)

INSTALLATION & SERVICE REFERENCE

INSTALLATION INSTRUCTIONS

 

Our continuing commitment to quality products may mean a change in specifications without notice.

©

  2015 - 2017

5151 San Felipe St., Suite 500, Houston, TX  77056

www.daikincomfort.com

IOD-4017C
6/2017

MODELS

RR20AVAK9/DX16SA0181XM
RR25AVAK9/DX16SA0241XM
RR30AVAK9/DX16SA0301XM
RR36AVAK9/DX16SA0361XM
RR42AVAK9/DX16SA0421XM

MODELS

FDMRN20AVAK

FDMRN25AVAK

FDMRN30AVAK

FDMRN36AVAK

FDMRN42AVAK

CONDENSING UNIT

EVAPORATIVE UNIT

Summary of Contents for RR20AVAK9

Page 1: ...einspecificationswithoutnotice 2015 2017 5151 San Felipe St Suite 500 Houston TX 77056 www daikincomfort com IOD 4017C 6 2017 MODELS RR20AVAK9 DX16SA0181XM RR25AVAK9 DX16SA0241XM RR30AVAK9 DX16SA0301XM RR36AVAK9 DX16SA0361XM RR42AVAK9 DX16SA0421XM MODELS FDMRN20AVAK FDMRN25AVAK FDMRN30AVAK FDMRN36AVAK FDMRN42AVAK CONDENSING UNIT EVAPORATIVE UNIT ...

Page 2: ...acturer assumes no responsibility for equipment installed in violation of any codes or regulations Rated performance is achieved after 72 hours of operation Rated performance is delivered at the specified airflow See outdoor unit specification sheet for split system models or product specification sheet for packaged and light commercial models Specification sheets can be found at www daikin ksa co...

Page 3: ...500 21 000 24 000 29 000 33 000 KW 4 83 6 15 7 03 8 50 9 67 Actual Cooling Input Power T1 1 Watts 1 385 1 769 2 154 2 615 3 120 Actual Cooling Input Power T3 2 Watts 1 833 2 333 2 667 3 222 3 667 Total Amps T1 1 Ampere 6 5 8 3 10 1 12 3 15 1 Total Amps T3 2 Ampere 8 0 10 3 12 4 15 0 18 3 EER T1 1 Btu h W 13 00 13 00 13 00 13 00 12 50 EER T3 2 Btu h W 9 00 9 00 9 00 9 00 9 00 Voltage Volt 230 230 2...

Page 4: ...gral part of the building foundation Ensure the foundation is sufficient to support the unit A concrete slab raised above ground level provides a suitable base Model Type A B C AA Residential 254 mm 10 254 mm 10 457 mm 18 508 mm 20 Light Commercial 305 mm 12 305 mm 12 457 mm 18 609 mm 24 Minimum Airflow Clearance Rooftop Installations If it is necessary to install this unit on a roof structure ens...

Page 5: ...ssor oil from ex isting systems lines and traps pay close attention to low areas where oil may collect NOTE If changing refrigerant types en sure the indoor coil and metering device is compatible with the type of refrigerant being used otherwise the indoor coil must be replaced Burying Refrigerant Lines If burying refrigerant lines can not be avoided use the following check list 1 Insulate liquid ...

Page 6: ...reases the chance of a refrigerant leak 2 Sweep the refrigerant line with nitrogen or inert gas during brazing to prevent the formation of copper oxide inside the refrigerant lines The POE oils used in R 410A applications will clean any copper oxide present from the inside of the refriger ant lines and spread it throughout the system This may cause a blockage or failure of the metering device 3 Af...

Page 7: ...present Check for leaks as previously indicated and repair as nec essary then repeat evacuation Electrical Connections The condensing unit rating plate lists pertinent electrical data necessary for proper electrical service and overcurrent protec tion Wires should be sized to limit voltage drop to 2 max from the main breaker or fuse panel to the condensing unit Consult the NEC CEC and all local co...

Page 8: ... wrench counterclockwise Open the valve until it con tacts the rolled lip of the valve body NOTE These are not back seating valves It is not necessary to force the stem tightly against the rolled lip Adequate refrigerant charge for the matching HSVTC evapora tor coil and 15 feet of lineset is supplied with the condensing unit If using evaporator coils other than HSVTC coil it may be necessary to a...

Page 9: ...auge manifold to base valve service ports Run system at least 10 minutes to al low pressure to stabilize 2 Temporarily install a thermometer 105 152 mm 4 6 from the compressor on the suction line Ensure the ther mometer makes adequate contact and is insulated for best possible readings Use vapor temperature to determine superheat 3 Refer to the superheat table provided for proper system superheat ...

Page 10: ...the Schrader ports for leaks and tighten valve cores if necessary Install caps finger tight SUCTION PRESSURE KPa SATURATED SUCTION TEMPERATURE ºC 615 3 3 641 2 2 668 1 1 695 0 724 1 1 753 2 2 783 3 3 813 4 4 847 5 6 879 6 7 912 7 8 946 8 9 NOTE SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE Dimensions and Weights Model Dimensions Weight W mm D mm H mm Equipm...

Page 11: ... SEE R ATING PLATE WIRING CODE FACTORY W IRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD W IRING HIGH VOLTAGE LOW VOLTAGE YL RD RD BK BK C T1 L1 T2 L2 RCCF F C HERM BR PU YL RD BK COMP IO CM AUX MAIN BK BR PU COLOR CODE BK BLACK BL BLUE BL PK BLUE PINK STRIPE BR BROWN OR ORANGE PU PURPLE RD RED WH WHITE YL YELLOW YL PK YELLOW PINK STRIPE GR GREEN NO TES 1 TO INDOOR UNIT TERMINAL BLOCK I...

Page 12: ...Voltage Test Voltage Faulty Evaporator Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage or Refrigerant Test For Leaks Add Refrigerant Restricted Liquid Line Replace Restricted Part Undersized Liquid Line Replace Line Undersized Suction Line Replace Line Not Enough Air across Indoor Coil Speed Blower ...

Page 13: ...13 THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 14: ...ing of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large loss of refrigerant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a condensing unit cover to protect the outdoor unit during the winter unless you first discuss i...

Page 15: ...TALL OR USE THE AIR CONDI TIONER UNIT IN A LAUNDRY ROOM DO NOT USE joined and twisted wires for incoming power supply This equipment is not intended for use in a potentially explosive atmosphere NOTICE DISPOSAL REQUIREMENTS Your air conditioning product is marked with this symbol This means the electrical and electronic products should not be mixed with unsorted household waste Do not try to disma...

Page 16: ... 359 1369 1326 1287 594 378 541 256 180 306 256 170 234 234 Model Dimensions in mm UNPACKING 1 After taking off the bands lift carton box 2 Remove the top cushion 3 Lift the unit and remove the bottom carton Unpacking the Evaporative Unit Dimensions Carton Box Top Cushion Indoor Unit Packing Bottom Figure 6 E K K B C D A A F M N L J G I E H Figure 7 ...

Page 17: ...t install the indoor unit where there is di rect sunlight on the unit and the location must be suitable for proper piping and drainage Main tain a suitable distance between doors and the unit Ceiling Concealed Mounting Use the hanger supplied with the unit Aluminum tape Field supplied Field Supplied Washer for hanger bracket attached Tighten Aluminum tape Field supplied DETAIL A See Detail A Insul...

Page 18: ...Model A mm inch L mm inch FDMRN20AVAK FDMRN25AVAK FDMRN30AVAK 1072 21 5 256 10 1 FDMRN36AVAK FDMRN42AVAK 1336 52 2 256 10 1 Provide clearance for servicing ease and optimal air flow as shown in Figure 11 A L Figure 10 10mm 300mm or more Can be smaller than 300mm if ceiling is removable Ceiling 2300mm or more Floor 300mm or more Figure 11 ...

Page 19: ...e area of the indoor unit Piping Works and Flaring Techniques Do not use contaminated or damaged copper tubing If any piping evaporator or condenser has been exposed or has been opened for 15 second or more the system must be vacuumed Generally do not remove plastic rubber plugs and brass nuts from the valves fittings tubings and coils until it is ready for connection If brazing work is required e...

Page 20: ... 2 5 2 0 Ǿ Tube D A mm Electrical Wire Connection All wires must be firmly connected Make sure none of the wires touch the refrigerant pipings compressor or any moving parts The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchor The power supply cord must be equivalent to H07RN F which is the minimum requirement Make sure no external pressure...

Page 21: ...ble on the market If refrigerant gas leakage occurs during installation or ser vicing be sure to ventilate fully If the refrigerant gas comes in contact with fire a poisonous gas may occur When installing or removing an air conditioner do not al low air or moisture to remain in the refrigerant cycle System Evacuation and Charging Evacuating vacuuming the system is necessary to eliminate all moistu...

Page 22: ... wiring has been done 4 Drainage check Pour water into left side of drain pan the water should drain from the right side of the unit TEST RUN 1 Conduct a test run of the unit after the water drainage test and gas leakage test have been completed 2 Confirm the following a Is the electrical plug firmly inserted into the socket b Are there any abnormal sounds coming from the unit c Is there a smooth ...

Page 23: ... substances or chemicals to clean the filter At least once every two weeks Clean more frequently if necessary Indoor Unit 1 2 Clean any dirt or dust on the grille or panel by wiping it with a soft cloth soaked in lukewarm water below 40 C Use only a neutral detergent solution Do not use gasoline volatile substances or chemicals to clean the filter At least once every two weeks Clean more frequentl...

Page 24: ...ng or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death Wiring is subject to change Always refer to the wiring diagram on the unit for the most up to date wiring Wiring Diagram ...

Page 25: ...25 APPENDIX LONG LINE SET APPLICATION R 410A ...

Page 26: ...lure to do so may cause property damage personal injury or death Before connecting tubing read the outdoor unit installation manual Pay particular attention to all safety precautions This long line set application guideline applies to all AHRI listed R 410A air conditioner and heat pump split system matches of nominal capacity 18 000 to 60 000 Btuh This guideline will cover installation requiremen...

Page 27: ...80 feet 24 4 m if the line set passes through a high ambient temperature zone 1 2 12 7 mm thick suction line insulation is required to reduce loss of capacity The liquid line must be insulated if more than 50 feet 15 2 m of liquid line will pass through an area that might reach temperatures of 30 F or higher than outdoor ambient Never attach a liquid line to any uninsulated portion of the suction ...

Page 28: ...l Strap Sleeve Strap Sleeve Wire Tie Wire Tie PVC Pipe Caulk Outside Wall Armaflex Wrapped Suction Line Liquid Line Wood Block Between Studs IMPORTANT Refrigerant lines must NOT come into contact with structure Fiberglass Insulation Wood Block Figure 1 2 Installation of Refrigerant Piping Vertical New construction shown NOTE If line set is installed on the exterior of an outside wall similar insta...

Page 29: ...it If subcooling at the indoor unit is less than 5 F then additional refrigerant must be added until this subcooling level is achieved If subcooling at the indoor unit is more than 7 F then refrigerant must be removed until this subcooling level is achieved Section 2 Outdoor Unit and Indoor Unit are at the Same Elevation Accessory Air Conditioner AC Heat Pump HP Crankcase Heater 40 watts minimum Y...

Page 30: ... 4 m The trap can be constructed of standard refrigerant fitting See Figure 3 1 1 Suction line must be sloped continuously towards the indoor unit 2 The maximum elevation vertical difference between the outdoor unit and indoor unit is a not restricted in this configuration for single stage air conditioning units must adhere to maximum equivalent length b 80 feet 24 4m for single stage heat pump un...

Page 31: ... Properly support and secure the inverted loop to the nearest point on the indoor unit or adjacent structure 4 An accumulator is required to be added external to the outdoor unit within 2 linear feet 61 linear centimeters of the outdoor unit for air conditioning installations See Table 4 1 for accumulator selection Adapter fittings at the accumula tor connection may be required Do NOT install an a...

Page 32: ... 6 45 0 7 0 8 1 Type of Elbow Fitting Inside Diameter in Table 5 1 Losses from suction line elbows equivalent length ft 3 4 7 8 1 1 8 90 short radius 0 5 0 6 0 7 90 long radius 0 5 0 5 0 5 45 0 2 0 2 0 3 Type of Elbow Fitting Inside Diameter in Table 5 2 Losses from suction line elbows equivalent length m Table 5 1 Losses from suction line elbows equivalent length ft EXAMPLE 3 4 suction line using...

Page 33: ...suction line is not approved for 2 ton two stage heat pump applications 3 7 8 suction line is not approved for 3 ton two stage heat pump applications over 80 feet 4 1 1 8 suction line is not approved for 4 ton and 5 ton two stage heat pump applications over 80 feet 7 6 15 2 22 9 30 5 38 1 45 7 53 3 61 0 68 6 76 2 1 2 0 99 0 97 0 96 0 94 0 94 0 93 0 93 0 92 0 91 0 89 5 8 1 00 0 99 0 99 0 99 0 98 0 ...

Page 34: ...re RA Initial additional refrigerant needed LA Actual lineal line set length Additional Refrigerant oz per lineal foot 3 8 liquid only 0 60 55 8 3 8 liquid and 5 8 suction 0 63 58 6 3 8 liquid and 3 4 suction 0 67 62 3 3 8 liquid and 7 8 suction 0 74 68 8 3 8 liquid and 1 1 8 suction 0 78 72 5 Line set sizes Additional Refrigerant g per lineal meter Table 5 5 Additional Refrigerant Per Unit Length...

Page 35: ...35 THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 36: ...of size or efficiency We have designed these units to significantly reduce the most frequent causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Better Quality NOTE SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHO...

Page 37: ...إجراء يتم قد 2015 2016 5151 San Felipe St Suite 500 Houston TX 77056 www daikincomfort com IOD 4017C AR 6 2017 الطرازات RR20AVAK9 DX16SA0181XM RR25AVAK9 DX16SA0241XM RR30AVAK9 DX16SA0301XM RR36AVAK9 DX16SA0361XM RR42AVAK9 DX16SA0421XM الطرازات FDMRN20AVAK FDMRN25AVAK FDMRN30AVAK FDMRN36AVAK FDMRN42AVAK التكثيف وحدة التبخير وحدة التركيب تعليمات ...

Page 38: ...تحمل وال التركيب مسؤول للطرازات المنتج مواصفات ورقة أو السبليت نظام لطرازات الخارجية الوحدة مواصفات ورقة انظر للهواء المحدد التدفق عند األداء تقييم ويتم التشغيل تحديد الرجاء www daikincomfort com أو www daikin ksa com الموقع على Daikin مواصفات أوراق على العثور يمكن والخفيفة المعبئة التجارية للوصول الحرارة مضخات أو الهواء مكيفات مثل تركيبه المراد المنتج لنوع الفرعية القائمة حدد ثم المواقع في التجار...

Page 39: ...0 230 230 230 230 60 60 60 60 60 2 807 2 381 2 013 1 743 2 211 8424 0 7060 5 5815 8 4776 3 3739 5 اﻟﺨﺎرﺟ اﻟﻄﺮاز اﻟﺪاﺧﻠ اﻟﻄﺮاز ﺗﺒﺮﻳﺪ ﻃﻦ 3 5 ﺗﺒﺮﻳﺪ ﻃﻦ 3 ﺗﺒﺮﻳﺪ ﻃﻦ 2 5 ﺗﺒﺮﻳﺪ ﻃﻦ 2 ﺗﺒﺮﻳﺪ ﻃﻦ 1 5 اﻟﺪاﺧﻠﻴﺔ اﻟﻮﺣﺪة اﻟﺨﺎرﺟﻴﺔ اﻟﻮﺣﺪة ﻣﺎﻟﻴﺰﻳﺎ ﻴﺔ اﻷﻣﺮﻳ اﻟﻤﺘﺤﺪة اﻟﻮﻻﻳﺎت ﺳﺎﻋﺔ ﺑﺮﻳﻄﺎﻧﻴﺔ ﺣﺮارﻳﺔ وﺣﺪة وات ﻛﻴﻠﻮ ﺳﺎﻋﺔ ﺑﺮﻳﻄﺎﻧﻴﺔ ﺣﺮارﻳﺔ وﺣﺪة وات ﻛﻴﻠﻮ وات وات أﻣﺒﻴﺮ أﻣﺒﻴﺮ وات ﺳﺎﻋﺔ ﺑﺮﻳﻄﺎﻧﻴﺔ ﺣﺮارﻳﺔ وﺣﺪة وات ﺳﺎﻋﺔ ﺑﺮﻳﻄﺎﻧﻴﺔ ﺣﺮارﻳﺔ وﺣﺪ...

Page 40: ...س على الوحدة تكون أن يجب األرضي الطابق مستوى على ينبغي ال الصوت انتقال إمكانية من للحد دفعها أو تغييرها يمكن ال بحيث من التأكد ينبغي منه ا ً ء جز أو المبنى ألساس ا ً مالمس األساس لوح يكون أن فوق المرفوع الخرسانة لوح ر ّ ف يو إذ الوحدة لدعم يكفي وحده األساس أن مناسبة قاعدة األرض سطح مستوى الهواء تدفق لخلوص األدنى الحد الطراز نوع A B C AA سكنية مم 254 بوصة 10 مم 254 بوصة 10 مم 457 بوصة 18 مم 508 بوص...

Page 41: ...قاسية الظروف في بوصة 1 2 والتلوث التلف من األنابيب تحمي بطريقة العازلة المادة تركيب يجب المترسب الضاغط زيت من الممكن القدر بتصريف قم أمكن وحيثما بدرجة االنتباه وينبغي والمحابس والوصالت الموجودة األنظمة من كنت إذا مالحظة الزيت فيها يتجمع قد التي المنخفضة بالمناطق أكبر وجهاز الداخلية اللفائف توافق من فتأكد التبريد غاز أنواع بتغيير تقوم استبدال عليك سيتوجب وإال المستخدم التبريد غاز نوع مع القياس الدا...

Page 42: ...لخدوش أو الشقوق من وخالية دائرية تكون بحيث وتنظيفها الحواف إزالة مع مربع بشكل التبريد غاز وصالت أطراف قطع يتم أن يجب التبريد غاز تسرب حدوث فرصة من يزيد آخر وضع 2 2 إستر بوليول زيوت ف ِ ُنظ ت وسوف التبريد وصالت داخل النحاس أكسيد تكون لمنع اللحام أثناء خامل بغاز أو بالنيتروجين التبريد وصلة أمأل انسداد في يتسبب قد وهذا النظام أنحاء كافة في وتنشرها التبريد غاز وصالت داخل الموجود النحاس أكسيد من أي R 4...

Page 43: ...1000 من ألكثر الضغط ارتفع إذا هو لما ًا ق وف باإلصالح وقم ًا ق مسب إليه مشار هو كما التسريبات من تحقق النتيجة نفس واجهت إذا 2 الخطوة إلى ارجع النظام في طفيف تسرب التفريغ كرر ثم مطلوب أعد ثم الضروري باإلصالح وقم ًا ق مسب إليه مشار هو كما التسريبات من تحقق تسرب وجود على يدل فهذا ميكرون 2000 عن الضغط ارتفع إذا التفريغ الكهربائية التوصيالت الصلة ذات بائية الكهر المعلومات التكثيف وحدة تصنيف لوحة تسرد و...

Page 44: ...ال التبريد غاز الصمام لجسم المدلفنة الشفة يالمس حتى الصمام افتح الساعة اتجاه عكس في السداسي الفتاح لف خالل من الساق واسحب الصمام المدلفنة الشفة عكس بالقوة الساق توجيه الضروري من ليس الخلفية القاعدة ذات الصمامات نوع من ليست الصمامات هذه مالحظة HSVTC المبخر للفائف كافية بصورة التبريد غاز شحن عملية توفير يتم التكثيف وحدة مع الواردة الوصالت مجموعة من ا ً قدم 15 و المتوافقة من يكون فربما HSVTC لفائف من...

Page 45: ... الوضع على التالي القسم في موضح هو كما الفائق التسخين أو الفائق التبريد نظام افحص المبدئي التشغيل تعليمات إتباع بعد للجهاز المستقر التشغيل بعد الثابتة الفوهة 1 1 خدمة بمنافذ الخدمة عداد مجمع ل ّ وص المقياس وصالت تطهير يستقر حتى دقائق 10 لمدة النظام بتشغيل قم الصمام القاعدة الضغط 2 2 6 4 ملم 152 105 مسافة على مؤقت بشكل ثرمومتر بتركيب قم توصيل من تحقق الشفط وصلة على الموجود الضاغط من بوصة القراءات أ...

Page 46: ... الطراز األبعاد الوزن مم العرض مم العمق مم االرتفاع المعدات KG وزن الشحن KG وزن DX16SA0181XMA RR20AVAK9 737 737 820 66 74 DX16SA0241XMA RR25AVAK9 737 737 820 65 73 DX16SA0301XMA RR30AVAK9 737 737 921 68 76 DX16SA0361XMA RR36AVAK9 737 737 972 74 82 DX16SA0421XMA RR42AVAK9 902 902 921 94 104 W D H ...

Page 47: ...قطب الملحق الرئيسي الملحق الرئيسي AMP 7 مصهر األرضية المعدات 3 مالحظة مصهر 1 مالحظة التحكم طرف كتلة األلوان رمز أسود BK أزرق BL وردي أو أزرق شريط BL PK بني BR برتقالي OR أرجواني PU أحمر RD أبيض WH أصفر YL وردي أصفر شريط YL PK أخضر GR المكون رمز الدائرة قاطع C الخارجية المروحة محرك CM الضاغط COMP المرتفع الضغط مفتاح HPS الداخلي الزائد الحمل IO المنخفض الكهربي الجهد تقاطع مربع LVJB المروحة و للضاغط ...

Page 48: ...ختبار المعطلة المبخر مروحة محرك استبدال أو إصالح أو باألرض الموصول المروحة محرك قصور به يوجد الذي المحرك لفات عدد اختبار المناسب غير التبريد متوقع المتوقع وحدة مقاومة افحص التبريد غاز أو القصر دائرة تبريد غاز إضافة التسريبات عن الكشف المسدودة السائل وصلة المسدود الجزء استبدل الحجم صغيرة السائل وصلة الوصلة استبدل الحجم صغيرة الشفط وصلة الوصلة استبدل الداخلي الملف عبر كافي هواء يوجد ال الثابت األترب...

Page 49: ...13 ا ً د عم فارغة ُركت ت الصفحة هذه ...

Page 50: ...ء تدفق تقييد يتسبب قد حيث المؤهلين الصيانة أفراد من غيره أو بك الخاص الموزع مع خططك مناقشة دون ا ً ي ضرور الخارجية اللفائف تنظيف أصبح إذا الهواء تدفق من ا ً أيض البقايا أو األوساخ وجود يحد قد حيث نظيفة الخارجية اللفائف على الحفاظ المهم فمن وبالمثل تكبد إلى النهاية في األنابيب في الصغيرة الثقوب أحد يتسبب وقد اللفائف في األنابيب بثقب الخبرة عديمي األفراد يقوم قد إذ المؤهلين الصيانة أفراد أحد باستئجا...

Page 51: ...مك وحدة تركيب تجنب مهمة مالحظة الغسيل غرف في الوارد الطاقة لمزود والملتوية المتداخلة األسالك استخدام تجنب حدوث ل َ حتم ُ ي التي األجواء في لالستخدام مصمم غير الجهاز هذا فيها انفجارات الجهاز من التخلص متطلبات مالحظة يعني وهذا الرمز هذا يحمل بك الخاص الهواء تكييف منتج إن منها التخلص عدم ينبغي واإللكترونية الكهربائية المنتجات ّ أن فرزها يتم لم التي المنزلية النفايات مع نظام بتفكيك يقوم من ّ إن حيث بن...

Page 52: ...غ األبعاد 6 الشكل 7 الشكل ّ الفك 1 1 الكرتون العلبة ارفع األربطة نزع بعد 2 2 العلوية الوسادة انزع 3 3 السفلي الكرتون وانزع الوحدة ارفع الكرتون العلبة العلوية الوسادة الداخلية الوحدة التغليف قاعدة E K K B C D A A F M N L J G I E H ...

Page 53: ...دة فيها تتعرض أماكن في الداخلية الوحدة تركيب تجنب ا ً ب مناس المكان يكون أن ويجب المباشرة الشمس ألشعة على حافظ مناسب نحو على والتصريف األنابيب لتوصيل والوحدة األبواب بين مناسبة فاصلة مسافة وجود بالسقف المخفي التركيب الوحدة مع المرفقة الة ّ الحم استخدم وزن لتحمل البنائية الناحية من كاف السقف ّ أن تأكد قة ّ ل المع الوحدة 9 الشكل 8 الشكل ...

Page 54: ...18 10 الشكل انظر المحور توسيط مسافة النحو على الهواء ولتدفق الصيانة لتسهيل فارغة مسافة اترك 11 الشكل في ح ّ موض هو كما األمثل 10 الشكل 11 الشكل A L ...

Page 55: ...نبوب المطاطية البالستيكية السدادات تزيل ال عام بوجه الكهربائية بالمكنسة إال واللفائف واألنابيب والتركيبات الصمامات من النحاسية والصواميل للتوصيل جاهزة تكون أن بعد غاز مرور من فتأكد النحاس لحام بأعمال القيام األمر اقتضى إذا ومن اللحام بأعمال القيام أثناء والوصالت األنابيب عبر النيتروجين لشبكة الداخلية الجدران على السخام ّن و تك على يقضي أن هذا شأن النحاسية األنابيب ّ إن حيث ببطء األنابيب قاطعة شفرة...

Page 56: ... المرفقة األسالك مرساة باستخدام المطلوب األدنى الحد وهو H07RN F الطاقة مزود سلك يكافئ أن يجب الطرفية واألسالك الموصالت على خارجي ضغط وجود عدم من تأكد ا ً صحيح ا ً ب تركي األغطية كل تركيب من تأكد الفجوات لتجنب األسالك لتوصيل د ّ ع مج شكل على المصمم المستدير الطرف استخدم المؤشر مع بمطابقتها األسالك ل ّ وص الطاقة مزود توصيل طرف الكهربائية التوصيالت مخطط راجع التوصيل طرف على الموجود للوحدة المرافق الط...

Page 57: ... األنابيب اختيار الضروري فمن R 22 التبريد غاز وحدات من أعلى األرفع النحاسية األنابيب استخدام تجنب صحيح نحو على النحاسية األسواق في توفرها من الرغم على ملم 0 8 من الصيانة أو التركيب أثناء التبريد لغاز تسريب حدوث حالة في قد النار مع التبريد غاز تالمس عند ا ً تمام المكان تهوية من فتأكد سام غاز ينتج في الرطوبة أو الهواء ببقاء تسمح ال فكه أو الهواء ف ّ ي مك تركيب عند التبريد غاز دورة وشحنه النظام تفريغ...

Page 58: ...ر الجانب في الماء اسكب التصريف اختبار األيمن الجانب من الماء يتدفق أن المفترض من الصرف للوحدة التجريبي التشغيل 1 1 الغاز تسريب واختبار المياه تصريف اختبار من االنتهاء بعد للوحدة تجريبي تشغيل بإجراء قم 2 2 يلي مما تأكد المقبس في بإحكام إدخاله تم الكهربائي التيار قابس هل أ الوحدة من عادية غير أصوات أي تصدر هل ب سلس نحو على المياه تصريف يتم هل ج التكثيف وحدة من دافئ هواء تدفق مع ف ّ ث المك مروحة تعمل...

Page 59: ...23 والصيانة الخدمة ...

Page 60: ... مخطط ﺃﺯﺭﻕ ﺃﺣﻤﺮ ﻣﺴﺘﺸﻌﺮ ﺍﻟﺮﺍﺟﻊ ﺍﻟﻬﻮﺍﺀ ﺗﻜﻤﻴﻠﻲ ﺃﺣﻤﺮ ﺃﺻﻔﺮ ﺭﻣﺎﺩﻱ ﺃﺯﺭﻕ ﺍﳋﺎﺭﺟﻴﺔ ﺍﻟﻮﺣﺪﺓ ﺇﻟﻰ ﻋﻠﻰ ﻟﻮﺣﺔ T ﺣﺮﻑ ﺷﻜﻞ ﲢﻜﻢ ﻭﺣﺪﺓ ﺃﻭ ﺳﻠﻜﻴﺔ ﻻﺳﻠﻜﻴﺔ ﺑﻨﻔﺴﺠﻲ ﺑﺮﺗﻘﺎﻟﻲ ﺑﻨﻲ ﻭﺭﺩﻱ ﻣﺴﺘﺸﻌﺮ ﺍﻟﺪﺍﺧﻠﻲ ﺍﳌﻠﻒ ﺃﺣﻤﺮ ﺑﻨﻔﺴﺠﻲ ﺃﺻﻔﺮ ﺭﻣﺎﺩﻱ ﺍﳌﻔﺘﺎﺡ ﺍﳌﻴﺪﺍﻧﻲ ﺍﻹﻣﺪﺍﺩ ﺗﻮﺻﻴﻞ ﻝ ﹼ ﺍﶈﻮ ﺍﻟﻐﺮﻓﺔ ﻋﺎﻟﻲ ﻣﺘﻮﺳﻂ ﻣﻨﺨﻔﺾ ﺣﻲ ﺗﻜﻤﻴﻠﻲ ﺍﳉﺰﺀ ﺭﻗﻢ 08 02 4 133319 ﺍﻟﻄﺮﺍﺯ FDMRN20 25 30 36 42AVAK FM L N N1 N2 CN2 CN5 CN6 ID OD L X ...

Page 61: ...410A R التكييف ألجهزة الطويلة الوصالت مجموعة استعمال الملحق 25 ...

Page 62: ...توى الحالية الممارسات بين تعارض وجود حالة في ذلك ومع الموجودة الممارسات تكملة هذا التركيب دليل في المدرجة بالتحذيرات قصد ُ ي هنا المدرجة للتحذيرات األولوية تكون الدليل السالمة احتياطات أحد الرمز هذا ل ِّ ث ُم ي الطويلة الوصالت مجموعة أقسام الفهرس 27 التكييف ألجهزة الطويلة الوصالت مجموعات استعماالت لجميع العامة المتطلبات 1 القسم 29 نفسه االرتفاع على والداخلية الخارجية الوحدتان 2 القسم 30 الداخلية ا...

Page 63: ...لل تمر الوصالت مجموعة كانت إذا م 24 4 ا ً قدم 80 عن طولها يزيد التي الطويلة الوصالت وصلة ستمر كان إذا السوائل وصلة عزل ويجب القدرة خسارة لتقليل الشفط وصلة في ملم 12 7 بوصة 2 1 مك ُ بس عازل استخدام فيجب تقم وال المحيطة الحرارة درجة من أعلى أو فهرنهايت درجة 30 إلى حرارتها درجة تصل قد منطقة عبر م 15 2 ا ً قدم 50 من أطول سوائل الشفط وصلة من معزول غير بقسم سوائل وصلة بتوصيل ا ً د أب بالفعل المصنع في تر...

Page 64: ...جهة في الوصالت مجموعة تركيب تم إذا مالحظة أفقي المبرد أنابيب شبكة تركيب 3 1 الشكل 28 دعامة جدار حمالة جلبة معدنية سوائل وصلة شفط وصلة Armaflex بـ مغلقة خارجي جدار بين خشبي قالب الدعامات خارجي جدار وصالت بـ مغلفة شفط Armaflex وصلة سوائل أنبوب عازل PVC الزجاجية األلياف من عازل هام الهيكل المبرد وصالت تلمس أن يجب ال قالب خشبي جلبة شفط وصلة سوائل وصلة سلكية ربط أدوات شريط سلكية ربط أدوات شريط سوائل وص...

Page 65: ...ا الفرعي التبريد مستوى إلى الوصول يتم حتى إضافي مبرد إضافة يجب الفرعي التبريد مستوى إلى الوصول يتم حتى المبرد إزالة يجب ٍ فعندئذ فهرنهايت نفسه االرتفاع على والداخلية الخارجية الوحدتان 2 القسم منها أدنى أو الخارجية الوحدة ارتفاع نفس على الداخلية الوحدة تكون حيث طويلة وصالت مجموعة باستخدام الكامل األفقي التركيب في 1 خالل الخارجية الوحدة إلى المبرد انتقال تقليل على يساعد بدوره وهذا الداخلية الوحدة نح...

Page 66: ...طلو الداخلية الوحدة في الزيت محبس يكون 1 3 الشكل راجع الداخلية الوحدة نحو متتابع بشكل الشفط وصلة إمالة يجب 1 هو الداخلية والوحدة الخارجية الوحدة بين ا ً ي عمود االرتفاع في فارق أقصى 2 األقصى المعادل بالطول االلتزام يجب المرحلة أحادية الهواء تكييف لوحدات التهيئة هذه في مقيد غير أ لـ م 61 قدم 200 يبلغ عمودي بفاصل سمح ُ ي استثناء المرحلة أحادية الحرارية المضخات لوحدات م 24 4 ا ً قدم 80 ب المرحلة أحاد...

Page 67: ...دة 4 القسم م 24 4 ا ً قدم 80 هو الداخلية والوحدة الخارجية الوحدة بين ا ً ي عمود االرتفاع في فارق أقصى 1 التالية 3 رقم المالحظة راجع الخارجية الوحدة إلى الداخلية الوحدة من السائل انتقال تمنع بطريقة الشفط وصلة تركيب يجب 2 للحلقة العلوي الطرف يكون أن يجب 1 4 الشكل راجع الداخلية الوحدة منفذ قبل الشفط وصلة على الشفط وصلة محبس تركيب يجب 3 شعاع بزاوية طويلتين مرفقيتين وصلتين لحم خالل من ببساطة إنشاؤه ويم...

Page 68: ...ت عن الناجمة الخسائر العمودي الطول األفقي الطول المكافئ الطول لقليل صحيح بشكل الشفط وصلة بقياس قم الشفط وصلة إلى االنحناءات إضافة من عليه الحصول تم الذي المكافئ الطول 1 5 الجدول يسرد 2 القدرة خسائر بالقدم المكافئ الطول الشفط لوصلة المرفقية الوصالت عن الناجمة الخسائر 1 5 الجدول بالمتر المكافئ الطول الشفط لوصلة المرفقية الوصالت عن الناجمة الخسائر 2 5 الجدول بالقدم المكافئ الطول الشفط لوصلة المرفقية ...

Page 69: ...5 0 95 0 94 0 0 93 8 7 1 00 0 99 0 99 0 99 98 0 98 0 98 0 98 0 97 0 97 0 4 8 1 1 1 00 1 00 1 00 1 00 1 00 1 00 1 00 1 00 0 99 0 99 60000 4 3 0 99 0 98 0 97 0 96 94 0 0 93 0 93 0 91 0 90 0 89 8 7 1 00 0 99 0 98 0 98 97 0 97 0 96 0 94 0 95 0 95 0 4 8 1 1 1 00 1 00 1 00 0 99 0 99 0 99 0 99 0 99 0 99 0 99 الوحدة حرارة وحدة الساعة في بريطانية الشفط طر ُ ق بالبوصة 1 بالمتر المعطي للطول القدرة مضاعف 7 6 ...

Page 70: ... 1 4 أرطال 3 حوالي توفر يلزم قد المستقيم الطول من م 45 7 قدم 150 أو و بوصة 8 1 1 الشفط في المعطاة الوصالت ألطوال اإلضافي المبرد على العثور ويمكن 3 5 الجدول استخدم المبرد الحتياجات الدقيقة الحسابات من لمزيد 4 5 الجدول قدم أونصة 0 6 قدم LA 15 أونصة RA متر جم 55 8 متر LA 4 6 جم RA حيث اإلضافية المبردات من الالزمة األولية الكمية RA الوصالت لمجموعة الفعلي المستقيم الطول LA الوحدة لطول ًا ق وف اإلضافي ا...

Page 71: ... ا ً د عم فارغة ُركت ت الصفحة هذه 35 ...

Page 72: ...حدة كل فحص يتم ا ً ر وأخي الجودة عالية ومكونات مواد نستخدم ونحن والتشغيل الصيانة بسهولة تتسم وهي كبير حد إلى ا ً شيوع األكثر المنتجات المصنع من خروجها جودتها في منتجاتنا من أفضل منتجات توجد ال شهرتنا سبب هو وهذا إشعار دون للتغيير هنا المدرجة األداء وبيانات المواصفات تخضع مالحظة 2017 2015 لألعوام النشر حقوق 77056 Houston TX 500 San Felipe St Suite 5151 www daikincomfort com 36 ...

Reviews: