30
4.
An accumulator is not required for air conditioners (accumulators are factory installed on heat pumps).
5.
An oil trap at the indoor unit is not required.
6.
Liquid Line Solenoid not required if non-bleed TXV is used on the outdoor unit.
SECTION 3. OUTDOOR UNIT IS ABOVE THE INDOOR UNIT
Accessory
Air Conditioner (AC)
Heat Pump (HP)
Crankcase Heater
(40 watts minimum)
Yes
Yes
Hard Start Assist
Yes
(See manual for each product)
Yes
(See manual for each product)
TXV (Indoor)
Yes
Yes
Liquid Line Solenoid at Outdoor
(Kit # LSK02*)
No
Yes *See Note 5
Inverted Refrigerant Trap at Indoor
No
No
Oil Trap at Indoor
Yes**
Yes**
**An oil trap at the indoor unit is required if the elevation diff erence exceeds 80' (24.4 m). The trap can be constructed of standard
refrigerant f itting (See Figure 3-1.)
1.
Suction line must be sloped continuously towards the indoor unit.
2.
The maximum elevation (vertical) difference between the outdoor unit and indoor unit is:
a. not restricted in this configuration for single stage air conditioning units (must adhere to
maximum equivalent length).
b. 80 feet (24.4m) for single stage heat pump units. Exception: 200ft (61 m) vertical separation allowed
for 14 SEER Long Line Set models and 16 SEER single stage HP models.
c. 25 feet (7.6 m) for two stage units.
3.
Inverted suction loop is not required at either unit.
4.
An accumulator is not required for air conditioners (accumulators are factory installed on heat pumps).
5.
Liquid Line Solenoid not required if non-bleed TXV is used on the outdoor unit.
Long Radius Street Ell
45°
Street Ell
Short Radius
Street Ell
45°
Ell
Figure 3-1. Oil Trap
Summary of Contents for RR20AVAK9
Page 13: ...13 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 25: ...25 APPENDIX LONG LINE SET APPLICATION R 410A ...
Page 35: ...35 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 49: ...13 ا ً د عم فارغة ُركت ت الصفحة هذه ...
Page 59: ...23 والصيانة الخدمة ...
Page 61: ...410A R التكييف ألجهزة الطويلة الوصالت مجموعة استعمال الملحق 25 ...