3
Unpacking the Unit
1. Pull the securing flap outwards until it is in line with the carton’s surface.
Securing Flap
Figure 1
2. Lift and remove the carton and the pad. Figure 2.
3. Remove hold-down brackets.
Carton
Pad
Literature
Packet
Hold-Down
Brackets
Figure 2
1.5TR
2TR
2.5TR
3TR
3.5TR
Outdoor Model
RR20AVAK9
RR25AVAK9
RR30AVAK9
RR36AVAK9
RR42AVAK9
Indoor Model
FDMRN20AVAK
FDMRN25AVAK
FDMRN30AVAK
FDMRN36AVAK
FDMRN42AVAK
Actual Cooling Capacity T1
(*1)
Btu/h
18,000
23,000
28,000
34,000
39,000
KW
5.27
6.74
8.20
9.96
11.43
Actual Cooling Capacity T3
(*2)
Btu/h
16,500
21,000
24,000
29,000
33,000
KW
4.83
6.15
7.03
8.50
9.67
Actual Cooling Input Power T1
(*1)
Watts
1,385
1,769
2,154
2,615
3,120
Actual Cooling Input Power T3
(*2)
Watts
1,833
2,333
2,667
3,222
3,667
Total Amps T1
(*1)
Ampere
6.5
8.3
10.1
12.3
15.1
Total Amps T3
(*2)
Ampere
8.0
10.3
12.4
15.0
18.3
EER T1
(*1)
Btu/h/W
13.00
13.00
13.00
13.00
12.50
EER T3
(*2)
Btu/h/W
9.00
9.00
9.00
9.00
9.00
Voltage
Volt
230
230
230
230
230
Frequency
Hertz
60
60
60
60
60
Refrigeration Charge
Kg
2.211
1.743
2.013
2.381
2.807
Annual Energy Consumption
KWh/Year
3739.5
4776.3
5815.8
7060.5
8424.0
Country of Origin
Indoor Unit
Malaysia
Outdoor Unit
United States of America
(*1) : Cooling capacity : Indoor 27°C DB / 19°C WB - Outdoor 35°C DB
(*2) : Cooling capacity : Indoor 29°C DB / 19°C WB - Outdoor 46°C DB
In
Summary of Contents for RR20AVAK9
Page 13: ...13 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 25: ...25 APPENDIX LONG LINE SET APPLICATION R 410A ...
Page 35: ...35 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 49: ...13 ا ً د عم فارغة ُركت ت الصفحة هذه ...
Page 59: ...23 والصيانة الخدمة ...
Page 61: ...410A R التكييف ألجهزة الطويلة الوصالت مجموعة استعمال الملحق 25 ...