12
Troubleshooting Information
Complaint
Unsatisfactory Cooling
POSSIBLE CAUSE
DOTS IN ANALYSIS
GUIDE INDICATE
"POSSIBLE CAUSE"
SYMP
T
O
M
Sy
st
em
wi
ll not s
tart
C
o
mpre
ss
or wi
ll n
o
t s
tart
- fa
n runs
C
o
mpre
ss
or and
C
o
nde
ns
e
r Fan
wi
ll not
s
tart
Ev
ap
orator fan will
not
s
tart
C
o
nde
ns
e
r fan
wi
ll no
t s
tart
C
o
mpre
ss
or runs
-
g
o
es
of
f on
ove
rload
C
o
mpre
ss
or c
yc
les
on
ove
rl
o
ad
Sy
st
em
ru
ns
c
o
nti
n
u
ous
ly
- l
it
tl
e c
o
ol
in
g
Too c
o
o
l a
nd th
en
too wa
rm
N
o
t c
o
ol
e
n
oug
h
on warm
da
ys
C
ertai
n are
as
to c
o
o
l ot
hers
to
warm
C
o
mp
re
ss
or
is
n
o
is
y
Lo
w
su
ct
io
n
p
re
ss
u
re
Lo
w
h
e
ad
p
res
su
re
H
igh
su
ct
io
n
p
re
ss
u
re
Hi
gh
he
ad p
re
ss
u
re
Test Method
Remedy
Power Failure
·
Test Voltage
Blown Fuse
·
·
·
Impact Fuse Size & Type
Loose Connection
·
·
·
·
Inspect Connection - Tighten
Shorted or Broken Wires
·
·
·
·
·
·
Test Circuits with Ohmmeter
Open Overload
·
·
Test Continuity of Overloads
Faulty Thermostat
·
·
·
·
Test Continuity of Thermostat and Wiring
Faulty Transformer
·
·
Check Control Circuit with Voltmeter
Shorted or Open Capacitor
·
·
·
·
Test Capacitor
Internal Compressor Overload Open
·
Test Continuity of Overload
Shorted or Grounded Compressor
·
·
Test Motor Windings
Compressor Stuck
·
·
Use Test Cord
Faulty Compressor Contactor
·
·
·
·
Test Continuity of Coil and Contacts
Faulty Fan Relay
·
Test Continuity of Coil and Contacts
Open Control Circuit
Test Control Circuit with Voltmeter
Low Voltage
·
·
·
Test Voltage
Faulty Evaporator Fan Motor
·
·
Repair or Replace
Shorted or Grounded Fan Motor
·
·
·
Test Motor Windings
Improper Cooling Anticipator
·
Check Resistance of Anticipator
Shortage or Refrigerant
·
·
·
·
Test For Leaks, Add Refrigerant
Restricted Liquid Line
·
·
·
·
Replace Restricted Part
Undersized Liquid Line
·
·
·
Replace Line
Undersized Suction Line
·
Replace Line
Not Enough Air across Indoor Coil
·
·
·
·
Speed Blower, Check Duct Static Pressure
Too Much Air across Indoor Coil
·
Reduce Blower Speed
Overcharge of Refrigerant
·
·
·
·
·
Recover Part of Charge
Noncondensibles
·
·
·
Recover Charge, Evacuate, Recharge
Recirculation of Condensing Air
·
·
·
Remove Obstruction to Air Flow
Infiltration of Outdoor Air
·
·
·
Check Windows, Doors, Vent Fans, Etc.
Improperly Located Thermostat
·
Relocate Thermostat
Air Flow Unbalanced
·
·
Readjust Air Volume Dampers
System Undersized
·
·
Refigure Cooling Load
Broken Internal Parts
·
Replace Compressor
Broken Valves
·
Test Compressor Efficiency
Inefficient Compressor
·
·
·
Test Compressor Efficiency
High Pressure Control Open
·
Reset and Test Control
Unbalanced Power, 3PH
·
·
·
Test Voltage
Wrong Type Expansion Valve
·
·
·
Replace Valve
Expansion Valve Restricted
·
·
·
·
·
·
Replace Valve
Oversized Expansion Valve
·
·
Replace Valve
Undersized Expansion Valve
·
·
·
·
·
Replace Valve
Expansion Valve Bulb Loose
·
·
Tighten Bulb Bracket
Inoperative Expansion Valve
·
·
·
Check Valve Operation
Loose Hold-down Bolts
·
Tighten Bolts
COOLING ANALYSIS CHART
No Cooling
System Operating
Pressures
For detailed service information refer to Remote Condensing Unit service manual.
Summary of Contents for RR20AVAK9
Page 13: ...13 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 25: ...25 APPENDIX LONG LINE SET APPLICATION R 410A ...
Page 35: ...35 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 49: ...13 ا ً د عم فارغة ُركت ت الصفحة هذه ...
Page 59: ...23 والصيانة الخدمة ...
Page 61: ...410A R التكييف ألجهزة الطويلة الوصالت مجموعة استعمال الملحق 25 ...