Check
Item
Expected Result
Actual Result
Lay out the pipes properly, and cannot
destroy the building structure and
waterproof.
Electric
verificatio
n
No cable is in contact with the copper pipe.
□ Passed □ Failed
Verify that the cables have been used
protective casing and the cable outlet facing
down.
Verify that the terminal position is higher
than the position of the connecting cable.
Verify that the phase sequence of the
outdoor unit output cables is correct. If the
phase sequence is incorrect, the outdoor fan
will rotate reversely.
The waterproof connector must be
tightened. Apply sealing putty when the
waterproof connector on the outdoor unit
side faces upward.
Low-
temperatu
re
componen
t
(optional)
The heating cable is connected.
□ Passed □ Failed
Cables are securely tightened, and measures
have been taken to prevent cables from sun
exposure and water.
The low-temperature component is secured
using bolts.
5.3 Checking the Water Cooling Module
Table 5-5 Installation checklist
Check Item
Expected Result
Actual Result
Rack
The rack is installed properly,
without any tilt.
□ Passed □ Failed
Pipes
Ports are connected correctly, and
all pipes are wrapped with thermal
insulation foam
□ Passed □ Failed
Electric
The power cables and signal cable
are connected as required.
□ Passed □ Failed
Cables are intact and not over-bent. □ Passed □ Failed
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
5 Verifying the Installation
Issue 05 (2020-10-10)
Copyright © Huawei Technologies Co., Ltd.
153