Chapter 3
Operation
3-15
Example 3:
Frequency command source
Setting data in F001 (Control panel) + multi speed select
Run command source
External signal (Control terminal)
(1) I/O connections
*) In case of SJ700D-****FUF3, you need to set C006=03 and C016=00.
*) You need to set multi speed frequency command into parameters (from A020 to A022).
*) Refer to 3.5.2 for changing the frequency command source and 3.5.3 for changing the run
command source.
(2) Operation
Frequency: By using the multi speed terminals, set the frequency command.
Run/Stop: Using the forward / reverse terminal to run and stop.
(3) Parameter settings
Parameter
Details
Setting data
A001
Digital Operator
A002
Control circuit terminal block
A020
Multi speed 1 and 2 are not active.
.
Note)
A021
Multi speed 1is active and
multi speed 2 is not active.
.
Note)
A022
Multi speed 1is not active and
multi speed 2 is active.
.
Note)
Note) Initial settings are 0.00Hz. You need to set the appropriate data.
FW
8
:
RV
CM1
Forward
7
:
CF1
6
:
CF2
P24
PLC
Reverse
Multi-speed1
Multi-speed2
CM1
P24
PLC
Sink logic
Source logic
V
R/L1
S/L2
T/L3
R
T
R0
T0
P
PD
N
RB
ELB
U
V
W
M
3-phase induction motor