4.2.37 Dynamic braking (BRD) function
The dynamic braking (BRD) function is provided in the inverter capacity
2.2kW or less models that have the built-in BRD circuit.
With this function, the energy regenerated by the motor is consumed by an
external resistor (i.e., the energy is converted to heat). You can effectively use
this function in your system, for example, to operate the motor as a generator by
rapidly decelerating the motor.
To use this function, make the following settings:
Item
Function code
Data or range of data
Description
Dynamic braking
usage ratio
b090 (*2)
0.0
Disabling the BRD operation
0.1 to 100.0 (%)
Setting of the dynamic braking usage ratio in units of
0.1%
The inverter will trip when the set rate is exceeded.
Usage rate (%) =
100
Dynamic braking
control
b095
00
Disabling the BRD operation
01
Enabling the BRD operation while the motor is running
Disabling the BRD operation while the motor is stopped
02
Enabling the BRD operation regardless of whether the
motor is running
Dynamic braking
activation level
b096
330 to 380 (V) (*1)
Level setting for 200 V class models
660 to 760 (V) (*1)
Level setting for 400 V class models
*1 The set dynamic braking activation level specifies the DC output voltage of the inverter's internal converter.
*2 Please refer to page 2-22 for 2.2.5 minimum resistance of connectable resistor and BRD ratio.
4.2.38 Cooling-fan operation setting
The cooling-fan operation setting function allows you to specify the operation
mode of the inverter's internal cooling fan. The cooling fan can be operated on a
constant basis or only while the inverter is driving the motor.
Item
Function code
Data or range of data
Description
Cooling fan control
b092
00
Specifying that the fan operates on a constant basis
01
Specifying that the fan operates only while the inverter
is driving the motor.
Note that the fan operates for 5 minutes after the
inverter power is turned on and after the inverter is
stopped.
Note: The cooling fan stops automatically when instantaneous power failure occurs or the inverter power is shut off
and resume the operation after power recovered. (Only inverter capacity 30kW or less models)
b090: Dynamic braking usage ratio
b095: Dynamic braking control
b096: Dynamic braking activation level
Related code
t2
ON
t1
t3
ON
ON
BRD
operation
100 seconds
100 seconds
(t1+t2+t3)
b092: Cooling fan control
Related code
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...