Chapter 3
Operation
3-12
(Operating procedure)
1) Confirm that all wirings are correct.
2) Turn on the earth-leakage breaker (ELB) to supply power to the inverter.
(The POWER lamp [red LED] of the digital operator goes on.)
3) Select the control circuit terminal block as the device to input frequency-setting commands by the frequency
source setting function.
- Display the function code "A001" on the monitor screen, and then press the key once.
(The monitor shows a 2-digit numeric value.)
- Use the and/or key to change the displayed numeric value to [01], and then press the
key once to specify the control circuit terminal block as the device to input frequency-setting commands.
(The display reverts to [A001].)
4) Select the control circuit terminal block as the device to input operation commands by the run command source
setting function.
- Display the function code "A002" on the monitor screen, and then press the key once.
(The monitor shows a 2-digit numeric value.)
- Use the and/or key to change the displayed numeric value to "01", and then press the
key once to specify the digital operator as the device to input operation commands.
(The display reverts to [A002].)
5) Set the monitor mode.
- To monitor the output frequency, display the function code "d001", and then press the key once.
(The monitor shows the output frequency.)
To monitor the operation direction, display the function code "d003", and then press the key once.
(The monitor shows for forward operation, for reverse operation, or for stopping.)
6) Start the motor operation.
- Set the FW signal (at the FW terminal on the control terminal block) to the ON level to start the motor.
(The RUN lamp [green LED] goes on.)
- Apply a voltage across the terminals O and L on the control circuit block to output the frequency corresponding
to the applied voltage from the inverter.
7) Stop the motor.
- Set the FW signal (at the FW terminal on the control terminal block) to the OFF level to decelerate and stop the
motor.
(When the motor stops, the RUN lamp [green LED] goes off.)
U
V
W
PD
P
RB
N
AL0
AL1
AL2
11
・・・・
CM2
15
SP
SN
RP
SN
G
H
L
O
H
Operating box
(OPE-4MJ2)
(OPE-8MJ2)
AMI
AM
L
O2
OI
O
P24
PLC
CM1
TH
FM
1
8
FW
R
S
T
R
S
T
ELB
(RV)
Type-D grounding (200 V class model)
Type-C grounding (400 V class model)
DC reactor
Motor
Braking unit
3-phase power
supply
Digital operator
FUNC
1
2
FUNC
1
2
STR
STR
FUNC
FUNC
Default: for sinking type