Item
Function code
Data or range of data
Description
Torque biasing mode
selection
P036
00
None
01
Bias setting from the digital operator
02
Bias setting via the O2 terminal (*1)
Torque bias setting
P037
-200 to +200 (%)
<-180 to +180>(*3)
Valid when "P036" = "01"
Torque biasing polarity
selection (*2)
P038
00
Depending on the sign of bias value
01
Depending on the motor rotation direction
*1 When the torque bias is set as a signal input via the O2 terminal, the inverter recognizes the signal voltage -10 to
+10 (V) as the bias value -200 to +200 (%).
*2 1) When "00" (depending on the sign of the bias value) is specified:
Regardless of the direction of motor rotation, torque in the forward direction increases when the torque bias
signal indicates a positive (+) value. Torque in the reverse direction increases when the torque bias signal
indicates a negative (-) value.
2) When "01" (depending on the motor rotation direction) is specified:
The sign of the bias value indicated by the torque bias signal and the direction of the torque biasing change
according to the rotation direction specified by the operation command.
With a forward operation command: the torque is generated in the same direction as that specified by the
sign of the torque bias value.
With a reverse operation command: the torque is generated in the opposite direction to that specified by the
sign of the torque bias value.
*3 <>:applied for 75 to 150kW
4.3.5 Torque control function
The torque control function is effective in the V2 control mode.
You can use the inverter not only under the speed control or pulse
train position control but also with this torque control function. You
can use this function effectively for inverter applications to, for
example, a winding machine.
To operate the inverter to drive the motor under torque control,
assign function "52" (ATR) to an intelligent input terminal. The torque
command input is enabled when the ATR terminal is on.
You can select one of four torque command input methods (digital
operator and three analog input terminals) by the torque command
input selection (P034).
Item
Function code
Data or range of data
Description
Torque command input selection
P033
00
Input from the O terminal
01
Input from the OI terminal
02
Input from the O2 terminal
03
Input from the digital operator
Torque command setting
P034
0 to 200 (%)
<0 to 180(%)>
Torque setting for the input from the digital
operator (P033 = 03)
Polarity selection at the torque
command input via the O2
terminal
P035
00
Depending on the sign of torque value
01
Depending on the motor rotation direction
Speed limit for torque-controlled
operation (forward rotation)
P039
0.00 to 99.99 or 100.0 to
400.0 (Hz)
Speed limit for torque-controlled
operation (reverse rotation)
P040
0.00 to 99.99 or 100.0 to
400.0 (Hz)
Torque biasing mode selection
P036
00
None
01
Bias setting from the digital operator
02
Bias setting via the O2 terminal
Torque bias setting
P037
-200 to +200 <-180 to 180>(%)
Valid when "P036" = "01"
Torque biasing polarity selection
P038
00
Depending on the sign of bias value
01
Depending on the motor rotation direction
Terminal function
C001 to C008
52
ATR: Permission for torque command input
*1 <>:applied for 75 to 150kW
P036: Torque biasing mode selection
P037: Torque bias setting
P038: Torque biasing polarity selection
d010: Torque bias monitoring
Related code
P033: Torque command input selection
P034: Torque command setting
P035: Polarity selection at the torque command
input via the O2 terminal
P039: Speed limit for torque-controlled operation
(forward rotation)
P040: Speed limit for torque-controlled operation
(reverse rotation)
d009/d010/d012: Torque command monitoring
P036: Torque biasing mode selection
P037: Torque bias setting
P038: Torque biasing polarity selection
d010: Torque bias monitoring
C001 to C008: Terminal [1] to [8] functions
Related code
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...