Chapter 2
Installation and Wiring
2-20
2.2.3 Wiring of the control circuit
(1) Wiring instructions
1) Terminals L and CM1 are common to I/O signals and isolated from each other.
Do not connect these common terminals to each other or ground them.
Do not ground these terminals via any external devices. (Check that the external devices connected to these
terminals are not grounded.)
2) Use a shielded, twisted-pair cable (recommended gauge: 0.75 mm
2
) for connection to control circuit terminals,
and connect the cable insulation to the corresponding common terminal. (Tightening torque: 0.7Nm,max
torque: 0.8Nm)
3) The length of cables connected to control circuit terminals must be 20 m or less. If the cable length exceeds 20
m unavoidably, you should use UP/DOWN function or current signal input with an isolation amplifier.
4) Separate the control circuit wiring from the main circuit wiring (power line) and relay control circuit wiring.
If these wirings intersect with each other unavoidably, square them with each other. Otherwise, the inverter may
malfunction.
5) Twist the cables connected from a thermistor to the thermistor input terminal (TH) and terminal CM1, and
separate the twisted cables from other cables connected to other common terminals. Since very low current
flows through the cables connected to the thermistor, separate the cables from those (power line cables)
connected to the main circuit. The length of the cables connected to the thermistor must be 20 m or less.
6) When connecting a contact to a control circuit terminal (e.g., an intelligent input terminal), use a relay contact
(e.g., crossbar twin contact) in which even a very low current or voltage will not trigger any contact fault.
7) When connecting a relay to an intelligent output terminal, also connect a surge-absorbing diode in parallel with
the relay.
8) Do not connect analog power supply terminals H and L or interface power supply terminals P24 and CM1 to
each other. Otherwise, the inverter may fail.
(2) Layout of control circuit terminals
H
O2
AM
FM
TH
FW
8
CM1
5
3
1
14
13
11
AL1
L
O
OI
AMI
P24
PLC
CM1
7
6
4
2
15
CM2
12
AL0
AL2
Terminal screw size: M3 (Tightening torque:0.7Nm,max torque:0.8Nm)
(3) Switching the input control logic
- In the factory setting, the input control logic for terminal FW and intelligent input terminals is the sink logic.
To switch the input control logic to the source logic, remove the jumper connecting terminals P24 and PLC on the
control circuit block, and then connect terminals PLC and CM1 with the jumper.
TH
PLC CM1 7
6
CM1
8
FW
Thermistor
PLC
5
4
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...