Chapter 4
Explanation of Functions
4-67
Item
Function code
Data or range of data
Description
Terminal function
C021 to C025
C026
33
LOG1: Logical operation result 1
(C142, C143, and C144)
34
LOG2: Logical operation result 2
(C145, C146, and C147)
35
LOG3: Logical operation result 3
(C148, C149, and C150)
Alarm relay
terminal function
36
LOG4: Logical operation result 4
(C151, C152, and C153)
37
LOG5: Logical operation result 5
(C154, C155, and C156)
38
LOG6: Logical operation result 6
(C157, C158, and C159)
Logical output
signal selection 1
C142/C145/C148/
C151/C154/C157
Selection of "00" to "56" from the data
(except LOG1 to LOG6) output to
intelligent output terminals
Selection of operation-target 1
Logical output
signal selection 2
C143/C146/C149/
C152/C155/C158
Selection of "00" to "56" from the data
(except LOG1 to LOG6) output to
intelligent output terminals
Selection of operation-target 2
Logical output
signal operator
selection
C144/C147/C150/
C153/C156/C159
00
AND
01
OR
02
XOR
4.2.67 Capacitor life warning signal (WAC)
The inverter checks the operating life of the capacitors on the internal
circuit boards on the basis of the internal temperature and cumulative
power-on time.
You can monitor the state of the capacitor life warning (WAC) signal by using the life-check monitoring function (d022).
If the WAC signal is output, you are recommended to replace the main circuit and logic circuit boards.
Item
Function code
Data or range of data
Description
Terminal function
C021 to C025
39
WAC: Capacitor life warning signal
(for on-board capacitors)
Alarm relay terminal function
C026
4.2.68 Communication line disconnection signal (NDc)
This signal function is enabled only when ModBus-RTU has been
selected for the RS485 communication.
If a reception timeout occurs, the inverter continues to output the
communication line disconnection signal until it receives the next data.
Specify the limit time for reception timeout by setting the communication trip time (C077).
For details, see Section 4.4, "Communication Functions."
Item
Function code
Data or range of data
Description
Terminal function
C021 to C025
32
NDc: Communication line
disconnection signal
Alarm relay terminal function
C026
Communication trip time
C077
0.00 to 99.99 (s)
Setting of the limit time for
reception timeout
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
C077: Communication trip time
Related code
(C077)
External control equipment
Inverter
Monitoring timer
Communication line disconnection
signal (NDc)
Communication trip time
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
Related code