Chapter 4
Explanation of Functions
4-73
4.2.81 FM terminal
You can monitor the inverter output frequency and output current via
the FM terminal on the control circuit terminal block. The FM terminal
is a pulse output terminal.
(1) FM siginal selection
Select the signal to be output from the FM terminal among those shown below.
If you select "03" (digital output frequency), connect a digital frequency counter to the FM terminal. To monitor other
output signals, use an analog meter.
Data
Description
Full-scale value
00
Output frequency (See Example 1.)
0 to maximum frequency (Hz) (*3)
01
Output current (See Example 1.)
0 to 200%
02
Output torque (*1) (See Example 1.)
0 to 200%
03
Digital output frequency (See Example 2.)
0 to maximum frequency (Hz) (*3)
04
Output voltage (See Example 1.)
0 to 133% (75% of full scale is equivalent to 100%)
05
Input power (See Example 1.)
0 to 200%
06
Electronic thermal overload (See Example 1.)
0 to 100%
07
LAD frequency (See Example 1.)
0 to maximum frequency (Hz)
08
Digital current monitoring (See Example 2.)
(*2)
09
Motor temperature (See Example 1.)
0°C to 200°C (0°C is output when the motor
temperature is 0°C or less.)
10
Heat sink temperature (See Example 1.)
0°C to 200ºC (0°C is output when the motor
temperature is 0°C or less.)
12
General analog YA (0) (See Example 1.)
0 to 100%
*1 This signal is output only when the V/F characteristic curve selection (see Section 4.2.18) is the sensorless vector
control, 0Hz-range sensorless vector control, or vector control with sensor.
(Example 1) When 00, 01, 02, 04, 05, 06, 07, 09, 10 or 12 is
slected
Cycle (T): Fixed (6.4 ms)
Duty (t/T): Varied
(Example 2) When 03 or 08 us selected
Cycle (T): Varied
Duty (t/T): Fixed (1/2)
*2 Digital current monitoring
If the output current matches the digital current monitor reference value (C030), the FM terminal will output a signal
indicating 1,440 Hz.
Item
Function code
Range of data
Description
Digital current monitor reference value
C030
"0.2 x rated current" to
"2.0 x rated current" (A)
Setting of the current for
1,440 Hz output
*3 The actually detected output frequency is output when the V/F characteristic curve selection is the vector control with sensor
(A044 = 05).
*4 For detail of the function, refer “Programming software EZ-SQ user manual”.
*5 When b086 (frequency scaling conversion facto is set, the value converted by gain is diplayed. (refer 4.1.7 Scaled output
frequency monitoring)
(2) FM terminal analog meter adjustment
Adjust the inverter output gain for the external meter connected to the FM terminal.
Item
Function code
Range of data
Description
[FM] terminal analog meter adjustment
C105
50. to 200. (%)
Setting of the gain for FM
monitoring
t
T
t
T
C027: [FM] siginal selection
b081: [FM] terminal analog meter
adjustment
C030: Digital current monitor reference
value
C105: [FM] terminal analog meter
adjustment
Related code
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...