Chapter 4
Explanation of Functions
4-146
(iii) List of registers (monitoring)
Register No.
Function name
Function code
R/W
Monitoring and setting items
Data
resolution
1001h
Output frequency monitoring
d001 (high)
R
0 to 40000
0.01 [Hz]
1002h
d001 (low)
1003h
Output current monitoring
d002
R
0 to 9999
0.1 [A]
1004h
Rotation direction minitoring
d003
R
0: Stopping, 1: Forward rotation, 2: Reverse rotation
0.1 [Hz]
1005h
Process variable (PV), PID
feedback monitoring
d004 (high)
R
0 to 9990
0.1
1006h
d004 (low)
1007h
Intelligent input terminal status
d005
R
2^0: Terminal 1 to 2^7: Terminal 8
1 bit
1008h
Intelligent output terminal status
d006
R
2^0: Terminal 11 to 2^4: Terminal 15
1 bit
1009h
Scaled output frequency
monitoring
d007 (high)
R
0 to 39960
0.01
100Ah
d007 (low)
100Bh
Actual-frequency monitoring
d008 (high)
R
-40000 to +40000
0.01 [Hz]
100Ch
d008 (low)
R
100Dh
Torque command monitoring
d009
R
-200 to +200
1 [%]
100Eh
Torque bias monitoring
d010
R
-200 to +200
1 [%]
100Fh
(Reserved)
-
-
Inaccessible
-
1010h
Torque monitoring
d012
R
-200 to +200
1 [%]
1011h
Output voltage monitoring
d013
R
0 to 6000
0.1 [V]
1012h
Power monitoring
d014
R
0 to 9999
0.1 [kW]
1013h
Cumulative power monitoring
d015 (high)
R
0 to 9999999
0.1
1014h
d015 (low)
1015h
Cumulative operation RUN time
monitoring
d016 (high)
R
0 to 999900
0.1
1016h
d016 (low)
1017h
Cumulative power-on time
monitoring
d017 (high)
R
0 to 999900
1 [h]
1018h
d017 (low)
1019h
Heat sink temperature
monitoring
d018
R
-200 to 2000
0.1 [°C]
101Ah
Motor temperature monitoring
d019
R
-200 to 2000
0.1 [°C]
101Bh
(Reserved)
-
-
Inaccessible
-
101Ch
101Dh
Life-check monitoring
d022
R
2^0: Capacitor on main circuit board
2^1: Low cooling-fan speed
1 bit
101Eh to
1025h
(Reserved)
-
-
Inaccessible
-
1026h
DC voltage monitoring (across P
and N)
d102
R
0 to 9999
0.1 [V]
1027h
BRD load factor monitoring
d103
R
0 to 1000
0.1 [%]
1028h
Electronic thermal overload
monitoring
d104
R
0 to 1000
0.1 [%]
1029h to
102Dh
(reserved)
-
-
Inaccessible
-
102Eh
User monitor 1
d025(HIGH)
R
-2147483647 to 2147483647
1
102Fh
d025(LOW)
R
1030h
User monitor 1
d026(HIGH)
R
-2147483647 to 2147483647
1
1031h
d026(LOW)
R
1032h
User monitor 1
d027(HIGH)
R
-2147483647 to 2147483647
1
1033h
d027(LOW)
R
1034h
Pulse counter
d028(HIGH)
R/W
0 to 2147483647
1
1035h
d028(LOW)
R/W
1036h
Position setting monitor
d029(HIGH)
R
-2147483647 to 2147483647
1
1037h
d029(LOW)
R
1038h
Position feedback monitor
d030(HIGH)
R
-2147483647 to 2147483647
1
1039h
d030(LOW)
R
103Ah to
1102h
Unused
-
Inaccessible
-
(iv) List of registers
Register No.
Function name
Function code
R/W
Monitoring and setting items
Data
resolution
1103h
Acceleration (1) time setting
F002 (high)
R/W 1 to 360000
0.01 [sec.]
1104h
F002 (low)
1105h
Deceleration (1) time setting
F003 (high)
R/W 1 to 360000
0.01 [sec.]
1106h
F003 (low)
1107h
Keypad Run key routing
F004
R/W 0 (forward rotation), 1 (reverse rotation)
-
1108h to
1200h
Unused
-
-
Inaccessible
-
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...