Chapter 4
Explanation of Functions
4-92
4.2.100 Torque limitation function
The torque limitation function allows you to limit the motor
output torque when "03" (sensorless vector control), "04"
(0Hz-range sensorless vector control), or "05" (vector control with
sensor) is specified for the V/F characteristic curve selection
(A044/A244).
You can select one of the following four torque limitation modes with the torque limit selection (b040):
1) Quadrant-specific setting mode
In this mode, individual torque limit values to be applied to four quadrants (i.e. forward powering, reverse
regeneration, reverse powering, and forward regeneration) are set as the torque limits 1 to 4 (b041 to b044),
respectively.
2) Terminal-switching mode
In this mode, the torque limit values set in the torque limits 1 to 4 (b041 to b044) are switched from one another
according to the combination of the states of torque limit switch terminals 1 and 2 (TRQ1 and TRQ2) assigned to
intelligent input terminals. A single selected torque limit is valid in all operating states of the inverter.
3) Analog input mode
In this mode, a torque limit value is set by a voltage applied to the control circuit terminal O2. The voltage range 0
to 10 V corresponds to the torque limit value range 0 to 200%. A single selected torque limit is valid in all
operating states of the inverter.
4) Option (option 1/2) mode
This mode is valid when the option board (SJ-DG) is used. For details on this mode, refer to the instruction manual
for the option board.
If function "40" (TL: whether to enable torque limitation) has been assigned to an intelligent input terminal, the
torque limitation mode selected by the setting of "b040" is enabled only when the TL terminal is turned on. When
the TL terminal is off, torque limit settings are invalid, and the maximum torque setting is applied as a torque limit.
If the TL function has not been assigned to any intelligent input terminal, the torque limitation mode selected by
the setting of "b040" is always enabled.
Each torque limit value used for this function is expressed as a ratio of the maximum torque generated when the
inverter outputs its maximum current on the assumption that the maximum torque is 200%. Note that each
torque limit value does not represent an absolute value of torque. The actual output torque varies depending on
the motor.
If the torque limited (TRQ) signal function is assigned to an intelligent output terminal, the TRQ signal will turn on
when the torque limitation function operates.
Item
Function code
Data or range of data
Description
V/F characteristic curve selection
A044/A244
03
Sensorless vector control
04
0Hz-range sensorless vector control
05
Vector control with sensor (not
available for A244)
Torque limit selection
b040
00
Quadrant-specific setting mode
01
Terminal-switching mode
02
Analog input mode
03
Option 1 mode
04
Option 2 mode
Torque limit (1)
b041
CT mode:
0 to 200 (%)
<0 to 180(%)>
VT mode:
0 to 150 (%)
<0 to 150(%)>
Forward powering (in quadrant-specific
setting mode)
Torque limit (2)
b042
Reverse regeneration (in quadrant-
specific setting mode)
Torque limit (3)
b043
Reverse powering (in quadrant-specific
setting mode)
Torque limit (4)
b044
Forward regeneration (in
quadrant-specific setting mode)
Terminal function
C001 to C008
40
Whether to enable torque limitation
41
Torque limit switch 1
42
Torque limit switch 2
Terminal function
C021 to C025
10
Torque limited signal
(NOTE) <>:applied for 75 to 150kW
A044/A244: V/F characteristic curve selection,
1st/2nd motors
b040: Torque limit selection
b041 to b044: Torque limits (1) to (4)
C001 to C008: Terminal [1] to [8] functions
C021 to C025: Terminal [11] to [15] functions
Related code
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...