Chapter 8
List of Data Settings
8-11
Code
Function name
Monitored data or setting
Default
Memo
Change during
RUN operation
Page
FF
FEF FUF
b031
≠
10 b031=10
Lev
el
s an
d
o
u
tp
u
t
ter
m
in
al
s
ta
tu
s
C038
Low-current indication signal
output mode selection
00 (output during acceleration/deceleration and constant-speed
operation), 01 (output only during constant-speed operation)
01
Not
Allowed
4-69
C039
Low-current indication signal
detection level
0.0 to 2.00 x "rated current" (A)
<0.0 to 1.80 x "rated current" (A) > (In case of CT)
0.0 to 1.50 x "rated current" (A) (In case of VT)
Rated current
Allowed Allowed
C040
Overload signal output mode
00 (output during acceleration/deceleration and constant-speed
operation), 01 (output only during constant-speed operation)
01
Not
Allowed
4-40
C041
Overload level setting
0.0 to 2.00 x "rated current" (A)
<0.0 to 1.80 x "rated current" (A) > (In case of CT)
0.0 to 1.50 x "rated current" (A) (In case of VT)
Rated current
Allowed Allowed
C042
Frequency arrival setting for accel.
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
Not
Allowed
4-62
C043
Frequency arrival setting for decel.
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
Not
Allowed
C044
PID deviation level setting
0.0 to 100.0 (%)
3.0
Not
Allowed 4-29
C045
Frequency arrival setting for
acceleration (2)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
Not
Allowed
4-62
C046
Frequency arrival setting for
deceleration (2)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
Not
Allowed
C052
Maximum PID feedback data
0.0 to 100.0 (%)
100.0
Not
Allowed
4-29
C053
Minimum PID feedback data
0.0 to 100.0 (%)
0.0
Not
Allowed
C055
Over-torque (forward-driving) level
setting
0. to 200. (%) <0. to 180. (%)>
100.
Not
Allowed
4-65
C056
Over-torque (reverse regenerating)
level setting
0. to 200. (%) <0. to 180. (%)>
100.
Not
Allowed
C057
Over-torque (reverse driving) level
setting
0. to 200. (%) <0. to 180. (%)>
100.
Not
Allowed
C058
Over-torque (forward
regenerating) level setting
0. to 200. (%) <0. to 180. (%)>
100.
Not
Allowed
C061
Electronic thermal warning level
setting
0. to 100. (%)
80.
Not
Allowed 4-38
C062
Alarm code output
00 (disabling), 01 (3 bits), 02 (4 bits)
00
Not
Allowed 4-65
C063
Zero speed detection level
0.00 to 99.99, 100.0 (Hz)
0.00
Not
Allowed 4-64
C064
Heat sink overheat warning level
0. to 200.0 (
C)
120.
Not
Allowed 4-68
Co
m
m
u
n
ic
at
io
n
f
u
n
ct
io
n
C071
Communication speed selection
02 (loopback test), 03(2400bps), 04(4800bps),
05(9600bps), 06(19.2kbps), 07(38.4kbps),
08(57.6kbps), 09(76.8kbps), 10(115.2kbps)
04
Not
Allowed
4-113
C072
Node allocation
1. to 247.
1.
Not
Allowed
C073
Communication data length
selection
7 (7 bits), 8 (8 bits)
7
Not
Allowed
C074
Communication parity selection
00 (no parity), 01 (even parity), 02 (odd parity)
00
Not
Allowed
C075
Communication stop bit selection
1 (1 bit), 2 (2 bits)
1
Not
Allowed
C076
Selection of the operation after
communication error
00 (tripping), 01 (tripping after decelerating and stopping the
motor), 02 (ignoring errors), 03 (stopping the motor after
free-running), 04 (decelerating and stopping the motor)
02
Not
Allowed
C077
Communication timeout limit
before tripping
0.00 to 99.99 (s)
0.00
Not
Allowed
C078
Communication wait time
0. to 1000. (ms)
0.
Not
Allowed
C079
Communication mode selection
00(ASCII), 01(Modbus-RTU)
00
Not
Allowed
A
d
ju
st
m
en
t
C081
[O] input span calibration
0. to 9999., 1000 to 6553(10000 to 65530)
Factory setting
Allowed Allowed
C082
[OI] input span calibration
Factory setting
Allowed Allowed
C083
[O2] input span calibration
Factory setting
Allowed Allowed
C085
Thermistor input tuning
0.0 to 999.9, 1000.
Factory setting
Allowed Allowed 4-72
C091
Debug mode enable
(Do not change this parameter, which is intended for factory
adjustment.)
00
Not
Not
O
th
e
rs
C101
Up/Down memory mode selection
00 (not storing the frequency data), 01 (storing the frequency data)
00
Not
Allowed 4-56
C102
Reset mode selection
00 (resetting the trip when RS is on),
01 (resetting the trip when RS is off),
02 (enabling resetting only upon tripping [resetting when RS is on]),
03(resetting only trip)
00
Allowed Allowed
4-54
C103
Restart mode after reset
00 (starting with 0 Hz), 01 (starting with matching frequency),
02 (restarting with active matching frequency)
00
Not
Allowed
M
et
er
a
d
ju
st
ment
C105
FM gain adjustment
50. to 200. (%)
100.
Allowed Allowed 4-73
C106
AM gain adjustment
100.
Allowed Allowed
4-74
C107
AMI gain adjustment
100.
Allowed Allowed
C109
AM bias adjustment
0. to 100. (%)
0.
Allowed Allowed
C110
AMI bias adjustment
20.
Allowed Allowed
(Note) <>indicate the setting range of 75 to 150kW
(Note) CT : Constant torque mode, VT : variable torque mode, you can set CT or VT by b049.
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...