Chapter 4
Explanation of Functions
4-138
(viii) Writes/Read data to multiple registers [17h]
This function writes/reads data to multiple registers.
(Example)
When setting "50.00 Hz" as the output frequency setting (F001) and reading the output frequency monitor (d001) in
the inverter at slave address "1":
*1) Note that the starting register address is 1 less than the actual address of the register to which the data is to be written first.
If the function to write/read data to multiple registers cannot be executed normally, the inverter will return an
exception response. For details, see Item (ix), "Exception response."
Query
Field name
Sample setting
(hexadecimal)
1
Slave address
01
2
Function code
17
3
Starting read register address (upper digit) (*1)
10
4
Starting read register address (lower digit) (*1)
00
5
Number of read registers (upper digit)
00
6
Number of read registers (lower digit)
02
7
Starting write register address (upper digit) (*1)
00
8
Starting write register address (lower digit) (*1)
00
9
Number of write registers (upper digit)
00
10
Number of write registers (lower digit)
02
11
Number of write data bytes
04
12
Updating data 1 (upper digit)
00
13
Updating data 1 (lower digit)
00
14
Updating data 2(upper digit)
13
15
Updating data 2(lower digit)
88
16
CRC-16 code (upper digit)
F4
17
CRC-16 code (lower digit)
86
Response
Field name
Sample setting
(hexadecimal)
1
Slave address
01
2
Function code
17
3
Number of read data bytes
04
4
Starting read register address (upper digit)
00
5
Starting read register address (lower digit)
00
6
Number of read registers (upper digit)
13
7
Number of read registers (lower digit)
88
8
CRC-16 code (upper digit)
E4
9
CRC-16 code (lower digit)
71
(register address) = (register number) - 1
(register address) = (register number) - 1
0000 1388h -> 5000d -> 50.00Hz
0000 1388h -> 5000d -> 50.00Hz