Chapter 3
Operation
3-18
3.5.2 Frequency command source selection
Key operation to set A001
****FF3
: Change A001 from 02 (operator) to 01 (control circuit terminal block).
Procedure
Key operation
Indication
Details
1-1
.
After powering up of the inverter, the operator displays 0.00,
output frequency monitor (d001)
1-2
Indication changes from data display (0.00) to parameter
display (d001).
1-3
or
Push the key and select the head of Group A.
1-4
Push the key and indication changes from A--- to A001.
1-5
Push the key and indication changes to 02(operator).
1-6
Push the key and change from 02 to 01 (control circuit
terminal block).
1-7
Push the key and indication changes A001 (Data save).
1-8
.
By pushing the key for more than three seconds,
indication changes to the output frequency data (d001).
****FEF3/FUF3
: Change from 01 (control circuit terminal block) to 02 (operator).
*) Replace the procedure 1-5 and 1-6 in the list above with 1-5’ and 1-6’ in the list below.
Procedure
Key operation
Indication
Details
1-5’
Push the key and indication changes to 01(control circuit
terminal block).
1-6’
Push the key and change the data to 02 (operator).
FUNC
FUNC
STR
FUNC
FUNC
1
2
2
1
FUNC