Chapter 4
Explanation of Functions
4-30
F002/F202/F302: Acceleration (1) time setting,
1st/2nd/3rd motors
F003/F203/F303: Deceleration (1) time setting,
1st/2nd/3rd motors
A092/A292/A392: Acceleration (2) time setting,
1st/2nd/3rd motors
A093/A293/A393: Deceleration (2) time setting,
1st/2nd/3rd motors
A094/A294: Select method to switch to Acc2/Dec2
profile, 1st/2nd motor
A095/A295: Acc1 to Acc2 frequency transition
point, 1st/2nd motors
A096/A296: Dec1 to Dec2 frequency transition
point, 1st/2nd motors
C001 to C008: Terminal [1] to [8] functions
Related code
4.2.24 Two-stage acceleration/deceleration function (2CH)
The two-stage acceleration/deceleration function allows you to change
the acceleration or deceleration time while the inverter is accelerating
or decelerating the motor.
Select one of the following three methods of changing the acceleration
or deceleration time:
1) Changing the time by the signal input to an intelligent input
terminal
2) Automatically changing the time when the output frequency
reaches a specified frequency
3) Automatically changing the time only when switching the motor
operation from forward rotation to reverse rotation, or vice
versa
Selecting the 3rd control system enables the change of the
acceleration or deceleration time only by terminal input. Not bytwo-stage acceleration/deceleration frequency.
To change the acceleration/deceleration time by the signal input to an intelligent input terminal, assign function "09"
(2CH) to one of the terminal functions C001 to C008.
Item
Function code
Data
Description
Acceleration (2) time
setting
A092/A292/
A392
0.01 to
3600. (s)
(See Examples 1 and 2.)
Deceleration (2) time
setting
A093/A293/
A393
0.01 to
3600. (s)
(See Examples 1 and 2.)
Select method to switch
to Acc2/Dec2 profile
A094/A294
00
Changing the time by the signal input to the 2CH terminal
(See Example 1.)
01
Changing the time at the two-stage acceleration/deceleration frequency (See
Example 2.)
02
Valid only while the inverter is switching the motor between forward and
reverse operations (See Example 3.)
Acc1 to Acc2 frequency
transition point
A095/A295
0.00 to
400.0 (Hz)
Valid when "01" is specified for the select method to switch to Acc2/Dec2 profile
(A094/A294) (See Example 2.)
Dec1 to Dec2 frequency
transition point
A096/A296
0.00 to
400.0 (Hz)
Valid when "01" is specified for the Select method to switch to Acc2/Dec2 profile
(A094/A294) (See Example 2.)
(Example 1) When "00" is specified for "A094" or "A294"
(Example 2) When "01" is specified for "A094" or "A294"
(Example 3) When "02" is specified for "A094" or "A294"
A092/
A292/
A392
2CH
FW
F002/
F202/
F302
F003/
F203/
F303
A093/
A293/
A393
Output
frequency
Acceleration
time 1
Acceleration
time 2
Deceleration
time 2
Deceleration
time 1
Output
frequency
Acceleration
time 1
Acceleration
time 2
Deceleration
time 2
Deceleration
time 1
FW
A096/A296
A095/A295
F003/
F203
A093/
A293
A092/
A292
F002/
F202
Output
frequency
Acceleration
time 1
Deceleration
time 2
Acceleration
time 2
Deceleration
time 1
FW
RV
F002/
F202
A093/
A293
A092/
A292
F003/