Chapter 4
Explanation of Functions
4-78
(4) Basic display mode
The monitor displays basic parameters. (The monitor display is the factory setting.)
The following table lists the parameters that can be displayed in basic display mode:
No.
Code displayed
Item
1
d001 to d104
Monitoring indication
2
F001
Output frequency setting
3
F002
Acceleration (1) time setting
4
F003
Deceleration (1) time setting
5
F004
Keypad Run key routing
6
A001
Frequency source setting
7
A002
Run command source setting
8
A003
Base frequency setting
9
A004
Maximum frequency setting
10
A005
[AT] selection
11
A020
Multispeed frequency setting
12
A021
Multispeed 1 setting
13
A022
Multispeed 2 setting
14
A023
Multispeed 3 setting
15
A044
V/F characteristic curve selection, 1st motor
16
A045
V/f gain setting
17
A085
Operation mode selection
18
b001
Selection of restart mode
19
b002
Allowable under-voltage power failure time
20
b008
Selection of retry after trip
21
b011
Retry wait time after trip
22
b037
Function code display restriction
23
b083
Carrier frequency setting
24
b084
Initialization mode (parameters or trip history)
25
b130
Overvoltage suppression enable
26
b131
Overvoltage suppression level
27
C021
Terminal [11] function
28
C022
Terminal [12] function
29
C036
Alarm relay active state
4.2.85 Initial-screen selection (selection of the initial screen to be displayed after power-on)
The initial-screen selection function allows you to specify the screen that is
displayed on the digital operator immediately after the inverter power is turned
on. The table below lists the screens (items) selectable. (The factory setting is
"01" [d001].)
To adjust the screen selection setting of your SJ700 series inverter to an SJ300 series inverter, select "00" (the screen
displayed when the STOP/RESET key was last pressed).
In case Automatic return to inirial display function is enabling, the monitor automatically displays the data selected
initial-screen selection without operating for 10 minutes.
Item
Function code
Data
Description
Initial-screen selection
b038
000
Screen displayed when the STR key was pressed last
(equivalent to the setting on SJ300)
001 to 060
Diplay data for the corresponding d001 to d060.
201
F001 (output current monitoring)
Automatic return to
initial display
b164
00
Disabling
01
Enabling(automatically transferring)
Note: When "000" (the screen displayed when the STR key was last pressed) has been selected, the monitor displays
code "*---" (entry to a group of functions) if the functional item displayed last is not "d***" or "F***".
(Example)
If the inverter power is turned off immediately after the setting of "A020" has been changed, the
monitor will display "A---" as the initial screen after the next power-on.
b038: Initial-screen selection
Related code
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...