Chapter 4
Explanation of Functions
4-13
4.2.12 Frequency operation function
The frequency operation function allows you to use the result of
an arithmetic operation on two frequency commands as the actual
frequency command or PID feedback data.
To use the operation result as the actual frequency command,
specify "10" for the frequency source setting (A001).
To use the operation result as the PID feedback data, specify "10" for the PV source setting (A076).
Item
Function code
Data
Description
Operation-target frequency
selection 1 and 2
A141/A142
00
Digital operator (A020/A220/A320)
(01)
Control on the digital operator
(Valid only when the OPE-SR is connected)
02
Input via the O terminal
03
Input via the OI terminal
04
Input via the RS485 terminal
05
Input from option board 1
06
Input from option board 2
07
Input of pulse train
Operator selection for frequency
operation
A143
00
Addition: (A141) + (A142)
01
Subtraction: (A141) - (A142)
02
Multiplication: (A141) x (A142)
Frequency source setting
A001
10
Output of operation result
PV source setting
A076
10
Output of operation result
Note 1: The [1] (up) and [2] (down) keys of the digital operator are ineffective when the frequency operation function
is enabled. Also, the frequency displayed by the output frequency monitoring (d001), Scaled output frequency
monitoring (d007), or output frequency setting (F001) cannot be changed with key operations.
Note 2: The settings of "A141" and "A142" can be the same.
f
O
f
O2
f
OI
+f
O2
0
AT
f
OI
0
0
f
O
+ f
O2
FW
FW
AT
f
OI
0
0
0
f
O
f
O2
f
O
+ f
O2
f
OI
+f
O2
(Example 1) When the
motor operation is not
reversible
Main frequency
command via the OI or
O terminal
Auxiliary
frequency
command via
the O2 terminal
Actual frequency
command
Forward
operation
Forward
operation
Reverse
operation
(Example 1) When the
motor operation is
reversible
Main frequency
command via the OI or
O terminal
Auxiliary
frequency
command via
the O2 terminal
Actual frequency
command
A141: Operation-target frequency selection 1
A142: Operation-target frequency selection 2
A143: Operator selection
A001: Frequency source setting
A076: PV source setting
Related code
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...