Chapter 4
Explanation of Functions
4-137
(vii) Writing data to multiple registers [10h]
This function writes data to sequential registers.
(Example)
When setting "3,000 s" as the Acceleration (1) time (F002) in the inverter at slave address "1":
Since register "1103h" and "1104h" to store the Acceleration (1) time (F002) have a data resolution of 0.01 seconds,
specify "300000" (493E0h) as the updating data to set "3,000 seconds".
If the function to write data to multiple registers cannot be executed normally, the inverter will return an exception
response. For details, see Item (viii), "Exception response."
Query
Field name
Sample setting
(hexadecimal)
1
Slave address (*1)
01
2
Function code
10
3
Starting register address (upper
digit) (*2)
11
4
Starting register address (lower
digit) (*2)
02
5
Number of registers (upper digit)
00
6
Number of registers (lower digit)
02
7
Number of data bytes (*3)
04
8
Updating data 1 (upper digit)
00
9
Updating data 1 (lower digit)
04
10
Updating data 2(upper digit)
93
11
Updating data 2(lower digit)
E0
12
CRC-16 code (upper digit)
9E
13
CRC-16 code (lower digit)
9F
*1 If this query is broadcasted, no inverter will return any response.
*2 Note that the starting register address is 1 less than the actual address of
the register to which the data is to be written first.
*3 As the number of bytes, do not specify the number of registers but the
number of bytes to be actually updated.
Response
Field name
Sample setting
(hexadecimal)
1
Slave address (*1)
01
2
Function code
10
3
Starting register address (upper
digit) (*2)
11
4
Starting register address (lower
digit) (*2)
02
5
Number of registers (upper digit)
00
6
Number of registers (lower digit)
02
7
CRC-16 code (upper digit)
E5
8
CRC-16 code (lower digit)
34
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...