Chapter 4
Explanation of Functions
4-72
4.2.78 Output signal delay/hold function
The output signal delay/hold function allows you to set on-delay and off-delay times for each
output terminal.
Since every output signal is turned on or off immediately when the relevant condition is
satisfied, signal chattering may occur if signal outputs conflict with each other. Use this
function to avoid such a problem by holding or delaying specific signal outputs.
To use this function, set on-delay and off-delay times for individual output terminals (a total
of six terminals, such as intelligent output terminals [11] to [15] and the alarm relay
terminal).
Output terminal
On-delay time
Off-delay time
11
C130
C131
12
C132
C133
13
C134
C135
14
C136
C137
15
C138
C139
RY(AL*)
C140
C141
Item
Function code
Range of data
Description
Output on
C130/C132/C134/
C136/C138/C140
0.0 to 100.0 (s)
Setting of on
Output off
C131/C133/C135/
C137/C139/C141
0.0 to 100.0 (s)
Setting of off
4.2.79 Input terminal response time
- The input terminal response time function allows you to
specify a sampling time for each of intelligent input
terminals 1 to 8 and the FW terminal. You can use this
function effectively to remove noise (e.g., chattering).
- If chattering hinders constant input from an input terminal, increase the response time setting for the input terminal. Note that an
increase in response time deteriorates the response. The response time can be set in a range of about 2 to 400 ms (corresponding
to settings of 0 to 200).
Item
Function code
Range of data
Description
Response time of intelligent
input terminals 1 to 8
C160-C167
0. to 200.
Variable in step of 1
FW terminal response time
C168
4.2.80 External thermistor function (TH)
The external thermistor function allows you to connect an external thermistor
installed in external equipment (e.g., motor) to the inverter,
and use the thermistor for the thermal protection of the external equipment.
Connect the external thermistor to control circuit terminals TH and CM1.
Make the functional settings according to the thermistor specifications as described below.
When using this function, the wiring distance between the inverter and motor must be 20 m or less. Since the thermistor current is
weak, isolate the thermistor wiring to the inverter from other wirings appropriately to prevent the thermistor signal from being
affected by the noise caused by other signal currents, including the motor current.
Item
Function code
Range of data
Description
Thermistor for thermal
protection control
b098
00
Disabling the external thermistor (TH) function
01
Enabling the TH function (resistor element with a
positive temperature coefficient [PTC])
02
Enabling the TH function (resistor element with a
negative temperature coefficient [NTC])
Thermal protection level
setting
b099
0 to 9999. (Ω)
Setting of the thermal resistance level (according to
the thermistor specifications) at which to trigger
tripping
Thermistor input tuning
C085
0.0 to 1000.
Setting for gain adjustment
Note: Specifying "01" for the thermistor for thermal protection control (b098) without an external thermistor
connected makes the inverter trip.
C130: Output 11 on-delay time
C131: Output 11 off-delay time
C132: Output 12 on-delay time
C133: Output 12 off-delay time
C134: Output 13 on-delay time
C135: Output 13 off-delay time
C136: Output 14 on-delay time
C137: Output 14 off-delay time
C138: Output 15 on-delay time
C139: Output 15 off-delay time
C140: Output RY on-delay time
C141: Output RY off-delay time
Related code
b098: Thermistor for thermal protection
control
b099: Thermal protection level setting
C085: Thermistor input tuning
Related code
C160 to C167: Response time of intelligent input terminals 1 to 8
C168: FW terminal response time
Related code
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...