Chapter 7
Specifications
7-3
(3) Common specifications of 200 V class and 400 V class models (continued)
Model name (type name)
SJ700D-****F
004
L
007
L/H
015
L/H
022
L/H
037
L/H
055
L/H
075
L/H
110
L/H
150
L/H
185
L/H
220
L/H
300
L/H
370
L/H
450
L/H
550
L/H
750
H
900
H
1100
H
1320/1500
H
O
pe
ra
ti
ng
en
vi
ro
nm
en
t
Ambient
temperature, storage
temperature(Note5),
humidity
-10
C to +50
C (ambient), -20
C to +65
C (storage), 20% to 90% RH (no condensation allowed)
Vibration tolerance
(See Note 1.)
5.9m/s
2
(0.6G),10
~
55Hz
2.94m/s
2
(0.3G),10
~
55Hz
Installation
environment
Environment without corrosive gases and dust, at an altitude of 1,000 m or less Note9)
Coating color
Grey
O
pt
io
na
l
bo
ar
ds
Feedback option
Vector control with sensor
Digital input option 4-digit BCD input, 16-bit binary input
DeviceNet option
Option to support the open-network DeviceNet function
Profibus-DP option
Option to support the open-network Profibus-DP function
Other optional components
LCD operator WOP, digital operator with potentiometer,
Braking resistor, AC reactor, DC reactor, Noise filter, Operator cables, Harmonic-wave suppressor unit,
LCR filter, Analog operation panel, Regenerative braking unit, Regenerative energy-saving unit,
Harmonics suppression unit, Controllers for various applications, PC tool ProdriveNext
Note 1: The vibration tolerance was tested in compliance with JIS C60068-2-6:2010 (IEC 60068-2-6:2007).
Note 2: The insulation distance complies with the UL and CE standards.
Note 3: The applicable motor refers to Hitachi standard 3-phase motor(4-pole).when using other motors, care must be taken to prevent the
rated motor current(50/60Hz)from exceeding the rated output current of the inverter.
Note 4: Function “64(EMR)”cannot be assigned to input terminal 3 by an operation from the operator. The function is automatically assigned to
the terminal when slide switch SW1 is set to ON.
Note 5: The storage temperature refers to the short-term temperature during transport.
Note 6: The frequency command will equal the maximum frequency at 9.8V for input voltage 0 to 10VDC, or at 19.8mA for input current 4 to
20mA.If this characteristic is not satisfactory for your application, contact your Hitachi sales representative.
Note 7: The analog voltage monitor and the analog current monitor are rough output values for analog meter connection.
The maximum output value might shift a little by the difference of the analog output circuit than 10V or 20mA.
Please inquire when there is a possibility that the inconvenience is caused.
Note8:
As for the range of the speed change, the variation range is different according to the installation situation and the characteristic and the
usage condition of the motor. Please inquire about details.
Note9: The density of air decreases by 1% whenever rising by 100m when the altitude exceeds 1000m. Therefore, it is necessary to decrease the
calorific value.
The calorific value of the main circuit semiconductor such as IGBT is proportional to the current and the voltage. Therefore,
please decrease by 1% and use the current rating every time it rises by 100m.
Please inquire about use in the high ground of 2500m or more.
Note10: When Sensor-less vector control is selected (A044=03), you may not obtain an intended starting torque or motor may trip depending
on the applied motor.
Note11: The inverter detects IGBT error (E30) as a protection function.
However IGBT error (E30) is not a protection for an output short circuit, therefore there is a possibility that IGBT will get damaged.
Moreover overcurrent error (E01 to E04) may be detected instead of IGBT error depending on the operational condition of an inverter.