Chapter 4
Explanation of Functions
4-7
4.2 Function Mode
4.2.1 Output frequency setting
The output frequency setting function allows you to set the inverter output
frequency.
You can set the inverter output frequency with this function (F001) only
when you have specified "02" for the frequency source setting (A001). For
other methods of frequency setting, see Section 4.2.4, "frequency source
setting (A001)."
(If the setting of function "A001" is other than "02", function "F001" operates as the frequency command monitoring
function.)
The frequency set with function "F001" is automatically set as the Multispeed frequency setting (A020). To set the
second and third multispeed s, use the multispeed frequency setting, 2nd motor, function (A220) and multispeed
frequency setting, 3rd motor, function (A320), or use function "F001" for the setting after turning on the SET and SET3
signals. For the setting using the SET and SET3 signals, assign the SET function (08) and SET3 function (17) to intelligent
input terminals.
If the set output frequency is used as the target data for the PID function, PID feedback data will be displayed in
percent (%). ("100%" indicates the maximum frequency.)
Item
Function code
Range of data
Description
Output frequency setting
F001
0.0, start frequency to
maximum frequency,
1st/2nd/3rd motors (Hz)
The frequency set with F001 is equal to the
setting of A020.
The second control frequency set with F001 is
equal to the setting of A220.
The third control frequency set with F001 is
equal to the setting of A320.
Multispeed 0
A020/A220/
A320
4.2.2 Keypad Run key routing
When you enter operation commands via the digital operator, the Keypad Run
key routing function allows you to select the direction of motor operation.
This function is ineffective when you use the control terminal block or remote operator to input operation commands.
Item
Function code
Data
Description
Keypad Run key routing
F004
00
Forward operation
01
Reverse operation
4.2.3 Rotational direction restriction
The rotational direction restriction function allows you to restrict the direction of
motor operation.
This function is effective regardless of the specification of operation command input device (e.g., control circuit block
or digital operator).
If an operation command to drive the motor in a restricted direction is input, the inverter (digital operator) will
display .
Item
Function code
Data
Description
Rotational direction
restriction
b035
00
Both forward and reverse operations are enabled.
01
Only forward operation is enabled.
02
Only reverse operation is enabled.
F001: Output frequency setting
A001: Frequency source setting
A020/A220/A320:
Multispeed frequency setting,
1st/2nd/3rd motors
C001 to C008:
Terminal [1] to [8] functions
Related code
F004: Keypad Run key routing
b035: Rotational direction restriction
Related code
Related code