Chapter 4
Explanation of Functions
4-33
4.2.27 Retry or trip after instantaneous power failure
(1) Retry (restart) after instantaneous power failure
- You can select tripping or retrying (restarting) the motor operation
as the inverter operation to be performed at the occurrence of
instantaneous power failure or undervoltage.
- If you specify a retry operation for the selection of restart mode
(b001), the inverter will retry the motor operation for the number
of times set as "b005" after an instantaneous power failure or the
number of times set as "b009" after overvoltage respectively, and
then trip if all retries fail. (The inverter will not trip if you specify
an unlimited number of retries.)
- With function "b004" you can select whether to make the inverter trip when an instantaneous power failure or
undervoltage occur while the inverter is in a stopped state.
- When selecting a retry operation, also set the retry conditions listed below according to the system to be driven by
the inverter.
- Even during a retry operation, the inverter will trip with error code "E09" (undervoltage) displayed if the
undervoltage status continues for 40 seconds.
Item
Function code
Data or range of data
Description
Selection of restart mode
(*4) (*6)
b001
00
Tripping
01
Restarting the motor with 0 Hz at retry
02
Starting the motor with a matching frequency at retry
(See Example 1.) (*3)
03
Starting the motor with a matching frequency at retry
The inverter trips after decelerating and stopping the motor.
(*1) (*3)
04
Restarting the motor with an input frequency at retry
(See Example 1.) (*3)
Allowable under-voltage
power failure time
b002
0.3 to 25.0 (s)
Restarting the motor when the power failure duration does
not exceed the specified time (See Example 1.)
Tripping when the power failure duration exceeds the
specified time (See Example 2.)
Retry wait time before motor
restart
b003
0.3 to 100. (s)
Time to wait until restarting the motor
Instantaneous power
failure/under-voltage trip
alarm enable (*2) (*4)
b004
00
Disabling the inverter from tripping
01
Enabling the inverter to trip
02
Disabling the inverter from tripping when the inverter is
stopped or while the motor is being decelerated or stopped
after the operation command has been turned off
Number of restarts on power
failure/under-voltage trip
events
b005
00
Retrying the motor operation up to 16 times after
instantaneous power failure
01
Retrying the motor operation an unlimited number of times
after instantaneous power failure
Restart frequency threshold
b007
0.00 to 400.0 (Hz)
Restarting the motor with 0 Hz if the frequency becomes
less than the frequency set here during motor free-running
(See Examples 3 and 4.)
Trip/retry selection
b008
00
Tripping
01
Restarting the motor with 0 Hz at retry
02
Starting the motor with a matching frequency at retry
03
Starting the motor with a matching frequency at retry
The inverter trips after decelerating and stopping the motor.
04
Restarting the motor with an input frequency at retry
Selection of retry count after
undervoltage
b009
00
Retrying the motor operation up to 16 times after
undervoltage
01
Retrying the motor operation an unlimited number of times
after undervoltage
Selection of retry count after
overvoltage or overcurrent
b010
1 to 3 (times)
Number of retries to be made after the occurrence of
overvoltage or overcurrent (*5)
Retry wait time after
overvoltage or overcurrent
b011
0.3 to 100. (s)
Time to wait until restarting the motor
Active frequency matching,
restart frequency select
b030
00
Frequency set when the inverter output has been shut off
01
Maximum frequency
02
Newly set frequency
Active frequency matching,
scan start frequency
b028
CT mode
0.20 to 2.00 x rated current
<0.20 to 1.80 x rated current>
VT mode
0.20 to 1.50 x rated current
<0.20 to 1.50 x rated current>
Current limit for restarting with active matching frequency
Active frequency matching,
scan-time constant
b029
0.10 to 30.00 (s)
Duration of frequency lowering when restarting with active
matching frequency
(NOTE) <>:applied for 75 to 150kW
b001: Selection of restart mode
b002: Allowable under-voltage power failure time
b003: Retry wait time before motor restart
b004: Instantaneous power failure/under-voltage
trip alarm enable
b005: Number of restarts on power
failure/under-voltage trip events
b007: Restart frequency threshold
b008: Selection of retry count after undervoltage
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
Related code