Chapter 3
Operation
3-16
Example 4:
Frequency command source
External analog voltage source and current source (Control terminal)
Run command source
External signal (Control terminal)
*) SJ700D-****FEF3/FUF3 (Initial settings)
(1) I/O connections
*) Refer to 3.5.2 for changing the frequency command source and 3.5.3 for changing the run
command source.
(2) Operation
Frequency: Using the voltage source and current source to set the frequency command with analog
select terminal (AT terminal: OFF: Voltage command / ON: Current command).
* AT terminal is used to switch the analog input O and OI to which the inverter refers as the
frequency command. (e.g. When AT terminal is OFF, the inverter outputs the frequency
according to the voltage input given to the O terminal)
Run/Stop: Using the forward / reverse terminal to run and stop.
(3) Parameter settings
Parameter
Details
Setting data
A001
Control circuit terminal block
A002
Control circuit terminal block
FW
8
:
RV
CM1
Forward
2
:
AT
P24
PLC
Reverse
Analog select
CM1
P24
PLC
Sink logic
Source logic
R/L1
S/L2
T/L3
R
T
R0
T0
P
PD
N
RB
OI
O
L
Voltage source
(0V to 10V)
Current source
(4mA to 20mA)
ELB
U
V
W
(+)
(-)
(+)
(-)
M
3-phase induction motor
9