Chapter 4
Explanation of Functions
4-38
(b) Constant-torque characteristic
Make this setting when driving a constant-torque motor with the inverter.
(Example) Setting on the SJ700D-150LFF3 (CT mode rated current: 64 A)
When "b012" is 64 A, and output frequency is 2.5 Hz:
(c) Free setting of electronic thermal characteristic
To protect the motor against overheating, you can set the electronic thermal characteristic freely according to the load
on the motor.
The range of setting is shown in the figures below.
Item
Function code
Range of data
Description
Free setting, electronic
thermal frequency (1) (2) (3)
b015/b017/
b019
0. to 400. (Hz)
Setting of frequency at each breakpoint
Free setting, electronic
thermal current (1) (2) (3)
b016/b018/
b020
0.0 (A)
Disabling the electronic thermal protection
0.1 to rated
current. (A)
Setting of the current at each breakpoint
(3) Thermal warning
You can configure this function so that the inverter outputs a warning signal before the electronic thermal protection
operates against motor overheat. You can also set the threshold level to output a warning signal with the electronic
thermal warning level setting (C061).
To output the warning signal, assign function "13" (THM) to one of the intelligent output terminals [11] to [15] (C021
to C025) and the alarm relay terminal (C026).
Item
Function code
Data
Description
Electronic thermal
warning level setting
C061
0.
Disabling the warning output
1. to 100. (%) (*1)
Setting of the threshold level to output the thermal
warning signal
*1 Set the ratio (%) of the warning level to the integrated value of the electronic thermal characteristic. A setting of
100% corresponds to the inverter trip due to overload (error code "E05").
X1.0
0
60
X0.9
X0.8
5
2.5
62.8
(98.1%)
86.4
(135%)
115.2
(180%)
60
3.0
0
Reduction
scale
Inverter output
frequency (Hz)
Trip time (s)
Motor current (A)
(Ratio to the rated
current of inverter)
A004/A204/A304
b020
b018
b016
b01
5
b017 b019
0
X1.0
5
40
X0.8
0
60
3.0
(x) (y)
(z)
0
Inverter output
frequency (Hz)
Range of
setting
(Example) When the output frequency is equal to
the setting of "b017"
(x): ("setting of b018"/"rated current") x 109%
(y): ("setting of b018"/"rated current") x 150%
(z): ("setting of b018"/"rated current") x 200%
Maximum frequency (Hz)
Trip time (s)
Output
current (A)