Chapter 4
Explanation of Functions
4-12
4.2.11 External analog input setting (O, O2, and OI)
The inverter has the following three types of external analog input terminals:
O-L terminal: 0 to 10 V
OI-L terminal: 4 to 20 mA
O2-L terminal: -10 to 10 V
The table below lists the settings of the external analog input terminals.
Item
Function
code
Data
Description
[AT]
selection
A005
00
Switching between the O and OI terminals
with the AT terminal
Turning on the AT terminal enables the OI-L terminal.
Turning on the AT terminal enables the O-L terminal.
01
Switching between the O and O2
terminals with the AT terminal
Turning on the AT terminal enables the O2-L terminal.
Turning on the AT terminal enables the O-L terminal.
(02)
(Valid only when the OPE-SR is used)
Switching between the O terminal and the
control with the AT terminal
Turning on the AT terminal enables the pot on OPE-SR
terminal.
Turning on the AT terminal enables the O-L terminal.
(03)
(Valid only when the OPE-SR is used)
Switching between the OI terminal and
the control with the AT terminal
Turning on the AT terminal enables the pot on OPE-SR
terminal.
Turning on the AT terminal enables the OI-L terminal.
(04)
(Valid only when the OPE-SR is used)
Switching between the O2 terminal and
the control with the AT terminal
Turning on the AT terminal enables the pot on OPE-SR
terminal.
Turning on the AT terminal enables the O2-L terminal.
[O2]
selection
A006
00
Using the O2 terminal independently
01
Using the O2 terminal for auxiliary frequency command (nonreversible) in addition to the O and OI
terminals
02
Using the O2 terminal for auxiliary frequency command (reversible) in addition to the O and OI
terminals
03
Disabling the O2 terminal
Note that whether frequency commands are input to the O2-L terminal and whether the motor operation is reversible
depend on the combination of settings of functions "A005" and "A006" and whether function "16" (AT) is assigned to
an intelligent input terminal as shown in the table below.
When the motor operation is reversible, the inverter operates the motor in a reverse direction if the sum of the
frequencies specified by the main frequency and auxiliary frequency commands is less than 0 (even when the forward
operation [FW] terminal is on). Even when no wire is connected to the 02 terminal, reverse operation of the motor
may occur and prolong the acceleration time if the output voltage fluctuates near 0 V.
A006
A005
AT
terminal
Main frequency command
Whether to input an auxiliary
frequency command
(via the O2-L terminal)
Reversible/
nonreversible
When the AT
function is
assigned to an
intelligent input
terminal
00,03
00
OFF
O-L terminal
No input
Nonreversible
ON
OI-L terminal
No input
01
OFF
O-L terminal
No input
ON
O2-L terminal
No input
Reversible
01
00
(Example 1)
OFF
O-L terminal
Input
Nonreversible
ON
OI-L terminal
Input
01
OFF
O-L terminal
Input
ON
O2-L terminal
No input
Reversible
02
00
(Example 2)
OFF
O-L terminal
Input
Reversible
ON
OI-L terminal
Input
01
OFF
O-L terminal
Input
ON
O2-L terminal
No input
When the AT
function is not
assigned to any
intelligent input
terminal
00
-
-
O2-L terminal
No input
Reversible
01
-
-
Addition of signals on O-L and
OI-L terminals
Input
Nonreversible
02
-
-
Addition of signals on O-L and
OI-L terminals
Input
Reversible
03
-
-
Addition of signals on O-L and
OI-L terminals
No input
Nonreversible
A005: [AT] selection
A006: [O2] selection
C001 to C008: Terminal [1] to [8] functions
Related code
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...