Chapter 4
Explanation of Functions
4-82
When using the brake control function, assign the following signal functions to intelligent input and intelligent output
terminals as needed.
(1) To input a signal indicating that the brake is released from the external brake to the inverter, assign the braking
confirmation signal (44: BOK) to one of the terminal [1] to [8] functions (C001 to C008).
(2) Assign the brake release signal (19: BRK), which is a brake-releasing command, to one of the intelligent output
terminals [11] to [15] (C021 to C025). To output a signal when braking is abnormal, assign the brake error signal
(20: BER) to an intelligent output terminal.
When using the brake control function, you are recommended to select the sensorless vector control (A044 = 03)
0Hz-range sensorless vector control (A044 = 04) or V2 (A044=05)as the V/F characteristic curve selection that ensures a
high starting torque. (See Section 4.2.18.)
Settings required for the brake control function
Item
Function code
Data or range of data
Description
Brake Control Enable
b120
00
Disabling the brake control function
01
Enabling the brake control function
Brake Wait Time for
Release
b121
0.00 to 5.00 (s)
Time to wait after the output frequency has
reached the release frequency until the
output current reaches the release current
Brake Wait Time for
Acceleration
b122
0.00 to 5.00 (s)
Mechanical delay after the release signal
has been output until the brake is released
Brake Wait Time for
Stopping
b123
0.00 to 5.00 (s)
Mechanical delay after the release signal
has been turned off until the brake is
applied
Brake Wait Time for
Confirmation
b124
0.00 to 5.00 (s)
Wait time longer than the delay after the
release signal output until the release
completion signal output from the brake is
input to the inverter
Brake Release
Frequency Setting
b125
0.00 to 99.99 or 100.0 to 400.0 (Hz)
Frequency at which to output the brake
release signal (*1)
Brake Release Current
Setting
b126
0.00 to 2.00 x rated current (%)
<0.00 to 1.80 x rated current (%)>
Frequency at which to permit brake
releasing (*2)
Only CT mode.
Braking frequency
b127
0.00 to 99.99 or 100.0 to 400.0 (Hz)
Frequency at which to apply the brake for
stopping the motor (*1)
*1 Specify a frequency higher than the start frequency (b082).
*2 Note that setting a low current may not ensure sufficient torque at brake releasing.
*3 <>:applied for 75 to 150kW
The inverter will trip with the braking error signal (BER) (E36: brake error) output in one of the following cases:
1) The inverter output current brake remains below the brake release current, even after the release wait time
(b121).
2) During acceleration, the braking confirmation signal (BOK) is not turned on within the braking wait time (b124).
During deceleration, the braking confirmation signal (BOK) is not turned off within the braking wait time (b124).
Otherwise, the braking confirmation signal is turned off although the brake release signal is output.
Summary of Contents for SJ700D-004L
Page 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Page 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Page 70: ...Chapter 3 Operation 3 25 Memo ...
Page 248: ...Chapter 5 Error Codes 5 11 Memo ...
Page 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...